Generator Failure
AGT 6000 PVMV-N 12V_24V - Chapter D: Generator Failure Page 79
D.1.3 Adjustment of the maximum upper revolution
1. Disconnect the plug at the electrical supply line of the actuator.
2. Unclamp the countering nut at the limitation screw with a wrench SW 10.
3. Connect an electrical voltage instrument (voltmeter) with a display range until 100V DC to the
clamps 7 and 8 of the VCS.
4. Be sure that no electrical load is adjusted.
5. Start the generator.
6. Increase the rev of the generator by turning the spindle of the actuator manually until the volt-
meter reach a value of 33V DC.
7. Turn the limit stop screw tight against the limit stop point at the rev regulator lever.
8. Protect the limit stop screw with the countering nut.
9. Check again if the voltage of the generator is limited to max. 33V without load.
The adjustment of the upper limitation of the rev serves an additional safety. The value of the
max. voltage lies 5V above the normal operating border.
01. Countering nut
02. Adjusting screw for upper limitation
03. Speed regulator lever
This adjustment should not be chan-
ged, otherwise the warranty expires.
Fig. D.1.3-1: revolution
02
03
01
Summary of Contents for AGT 6000 PVMV-N
Page 1: ...Panda AGT 6000 PVMV N Super silent technology 24V 6kW Fischer Panda GmbH ...
Page 6: ......
Page 10: ...8 Socket wrench set Hexagon wrench keys ...
Page 92: ...Generator Failure Page 90 AGT 6000 PVMV N 12V_24V Chapter D Generator Failure ...
Page 100: ...Appendix Page 98 AGT 6000 PVMV N 12V_24V Chapter E Appendix ...
Page 102: ...Page 100 AGT 6000 PVMV N 12V_24V Chapter E E 6 Capsule Measurements ...
Page 106: ...VCS AGT U I Page 104 Chapter A VCS AGT U I VCS AGT UI_eng fm Fischer Panda Datasheet blank ...