Battery monitor in DIN-tracks housing (RE9517)
Anleitung_RE9517_eng.fm
Kapitel/Chapter A: Battery monitor in DIN-tracks housing (RE9517) - Seite/Page 107
Fischer Panda Datenblatt/Datasheet
• charge conclusion delay time: 10min - 2h
• tolerance of the delay time: ± 20%
The adjusted value for charge conclusion voltage can be based on the clamp 3 against clamp 2 (minus). The adju-
sted value for battery undervoltage can be based on the clamp 4 against clamp 2 (minus). In each case the opera-
tion voltage per cell is measured. Absolute operation voltage can be determined, by multiplying measured voltage
with the number of cells. For the measurement use only a multimeter with an impedance
≥
10MOhm, since other-
wise substantial measuring errors arise.
Direction of rotation of the trimmers: Turn in the clockwise direction = larger value
By a drilling below clamp 1 is accessible with a small screwdriver a tracer, which makes it possible, for test purpo-
ses, to switch between the two switching status back and forth. This functioned however only if the battery voltage is
within the adjusted borders. Outside of the limit values the battery guard cannot be affected by the tracer.
Connction examples: Connection to AGT-Panel
The cable connection between battery monitor and control panel must be implemented as twisted or shielded cable.
Relay switch RE0003 for Batterymonitor Fischer Panda Art.No.: F1RORE0003
Ad-on for the Batterymonitor RE9517 (with transistor out) to get a Relayswitch
If the Batterymonitor recognice Bat-Low (LED turn on) the Relay switch close. For additional information see
RE0003 Datasheet
Battery monitor
AGT-Panel
clamp 7
clamp 14
Output -
clamp 8
clamp 13
A.5 Additional products
Summary of Contents for AGT 6000 PVMV-N
Page 1: ...Panda AGT 6000 PVMV N Super silent technology 24V 6kW Fischer Panda GmbH ...
Page 6: ......
Page 10: ...8 Socket wrench set Hexagon wrench keys ...
Page 92: ...Generator Failure Page 90 AGT 6000 PVMV N 12V_24V Chapter D Generator Failure ...
Page 100: ...Appendix Page 98 AGT 6000 PVMV N 12V_24V Chapter E Appendix ...
Page 102: ...Page 100 AGT 6000 PVMV N 12V_24V Chapter E E 6 Capsule Measurements ...
Page 106: ...VCS AGT U I Page 104 Chapter A VCS AGT U I VCS AGT UI_eng fm Fischer Panda Datasheet blank ...