3.3.2 Connecting the operating voltage and the I/Os
WARNING
Use only power units which guarantee reliable isola-
tion of the operating voltages as per IEC 742/EN
60742/VDE 0551 with at least 4 kV isolation resist-
ance. Switch power packs are permitted, providing
they guarantee reliable isolation in accordance with
EN 60950/VDE 0805.
By using PELV power units, protection against electric
shock (protection against direct and indirect contact) in
accordance with EN 60204-1 / IEC 204 is guaranteed
on the SPC-10. Safety transformers with the adjacent
designation must be used for supplying PELV networks.
The SPC-10 must be earthed in order to ensure that it
functions correctly (e.g. EMC).
CAUTION
Connect the earth connection on the left-hand side
of the housing with low impedance (short cable with
large cross-sectional area) to the earth potential.
In this way, you will avoid interference caused by elec-
tromagnetic influences.
PLEASE NOTE
Use only the original cable type KSPC10-SPS-10 for
connecting the voltage supply and the I/Os.
3. Installation
3-26
SPC-10 9902a
Summary of Contents for SPC-10 Series
Page 1: ...Smart Soft Stop SPC 10 Electronic Pneumatic ...
Page 3: ...Order no 170 363 Title Manual Designation P BE SPC10 GB II SPC 10 9902a ...
Page 9: ...VIII SPC 10 9902a ...
Page 10: ...Chapter 1 Summary of system 1 Summary of system SPC 10 9902a 1 1 ...
Page 18: ...Chapter 2 Fitting 2 Fitting SPC 10 9902a 2 1 ...
Page 19: ...Contents 2 Fitting 2 1 Fitting the SPC 10 2 3 2 Fitting 2 2 SPC 10 9902a ...
Page 22: ...Chapter 3 Installation 3 Installation SPC 10 9902a 3 1 ...
Page 52: ...Chapter 4 Commissioning 4 Commissioning SPC 10 9902a 4 1 ...
Page 62: ...Chapter 5 Diagnosis and error treatment 5 Diagnosis and error treatment SPC 10 9902a 5 1 ...
Page 74: ...Appendix A Technical appendix Technical appendix SPC 10 9902a A 1 ...