5.2 Operating faults
1) Slide does not move
Cause
Remedy
Remarks
No supply pressure
Check
5...7 bar required
Valve cable not connected correctly
Check
See section 3.3.3
Proportional directional control valve
is defective
Check and replace
if necessary
Look through inspection
window to see if slide
jams
1)
1) See operating instructions for valve MPYE-5-...
2) Bad behaviour during move to end position
Cause
Remedy
Remarks
System is not fitted correctly
Check fitting and
mechanical parts
Check potentiometer
and cylinder for
parallelism, mechanical
play and tightness
System is not earthed correctly
Check
See chapter 3
Incorrect DIL switch setting
Check DIL switch
setting
See appendix A.1
High fluctuation of supply pressure
(> 0.5 bar)
Check supply
pressure
If necessary fit
compressed air reservoir
Non-permitted mass load
Check mass load
and DIL switch
setting
Place a basic load on
the slide so that the
value range is
maintained when
positioning is made with
different masses
Movement to end position too fast/hard
Increase cushioning
See section 5.3
Movement to end position too slow/soft
Reduce cushioning
See section 5.3
5. Diagnosis and error treatment
SPC-10 9902a
5-5
Summary of Contents for SPC-10 Series
Page 1: ...Smart Soft Stop SPC 10 Electronic Pneumatic ...
Page 3: ...Order no 170 363 Title Manual Designation P BE SPC10 GB II SPC 10 9902a ...
Page 9: ...VIII SPC 10 9902a ...
Page 10: ...Chapter 1 Summary of system 1 Summary of system SPC 10 9902a 1 1 ...
Page 18: ...Chapter 2 Fitting 2 Fitting SPC 10 9902a 2 1 ...
Page 19: ...Contents 2 Fitting 2 1 Fitting the SPC 10 2 3 2 Fitting 2 2 SPC 10 9902a ...
Page 22: ...Chapter 3 Installation 3 Installation SPC 10 9902a 3 1 ...
Page 52: ...Chapter 4 Commissioning 4 Commissioning SPC 10 9902a 4 1 ...
Page 62: ...Chapter 5 Diagnosis and error treatment 5 Diagnosis and error treatment SPC 10 9902a 5 1 ...
Page 74: ...Appendix A Technical appendix Technical appendix SPC 10 9902a A 1 ...