B Reference
paramete
98
Festo – GDCP-CMMO-ST-LK-C-HP-EN – 2017-05b – English
PNU 104
Required software version (Required Software Version)
Subindex 1
Class: Var
Data type: uint16
FW …
Access: ro
Reading of the FCT version, which is required for operation of the firmware. The min. version number
of the Festo Configuration Tool (FCT) consists of 4 numerals (e.g. “xxyy”).
Format (16 bit, BCD)
Numerals
Significance
xx
Main version number
yy
Secondary version number
Tab. B.12
PNU 104
B.4.3
Device data – identification
PNU 115
Controller type (Controller Type)
Subindex 1 … 5
Class: Array
Data type: uint8
FW …
Access: ro
Reading of the configuration of the motor controller.
Subindex 1
Motor technology (Motor Technology)
Technology of the motor
Value
Significance
0x02 (2)
Stepper motor (-ST)
Subindex 2
Nominal current class (Nominal Current Class)
Nominal current of the motor controller
Value
Significance
0x02 (2)
5 A (-C5)
Subindex 3
Voltage class (Voltage Class)
Voltage class of the motor controller
Value
Significance
0x01 (1)
24 V (-1)
Subindex 4
Fieldbus interface (Field Bus Interface)
Bus interface of the motor controller
Value
Significance
0x09 (9)
IO-Link
Subindex 5
Design of digital inputs/outputs (Digital In/Outputs)
Value
Significance
0x01 (1)
PNP (-P)
Tab. B.13
PNU 115
Summary of Contents for CMMO-ST-C5-1-LKP