Festo – GDCP-CMMO-ST-LK-C-HP-EN – 2017-05b – English
PNU 1017
Damping time, stop detection (Block Detection Window Time)
Subindex 1
Class: Var
Data type: uint16
FW …
Access: rw2
Reading or parameterisation of the damping time [ms] for stop detection in homing (homing method:
stop).
Tab. B.133 PNU 1017
B.4.22
Axis parameter: electrical drives 1 – controller parameters
PNU 1022
Target message window reached (Position Target Window)
Subindex 1
Class: Var
Data type: int32
FW …
Access: rw2
Reading or parameterisations of the target [SINC]
by which the current position may deviate from the
target position while still interpreted to be within the target window.
The range of the message window is double that of the parameterised value. The setpoint/target
position is in the centre of the window.
Tab. B.134 PNU 1022
PNU 1023
Damping time for target reached (Position Target Window Time)
Subindex 1
Class: Var
Data type: uint16
FW …
Access: rw2
Reading or parameterisation of the damping time [ms].
The damping time begins when the target position window is reached. If the actual position has been
in the target position window after the damping time has expired, the SPOS.MC bit is set.
Tab. B.135 PNU 1023