B Reference
paramete
134
Festo – GDCP-CMMO-ST-LK-C-HP-EN – 2017-05b – English
B.4.18
Project data – direct mode general
PNU 581
Torque limitation (Torque Limitation)
Subindex 1
Class: Var
Data type: int16
FW …
Access: rw1
Reading or parameterisation of the max. force [‰ force basic value, PNU 555] for the direct mode
position and speed.
– 0 = no motor current (0 A)
– 1000 = force basic value, PNU 555
The value is valid for the positive and negative direction of rotation.
Tab. B.106 PNU 581
PNU 582
Start delay (Start Delay)
Subindex 1
Class: Var
Data type: uint32
FW …
Access: rw1
Reading or parameterisation of the start delay times [ms]. The time is started with the Start com
mand. After the time has elapsed, travel is started.
Tab. B.107 PNU 582
PNU 583
Start condition (Start Condition)
Subindex 1
Class: Var
Data type: uint8
FW …
Access: rw1
Reading or parameterisation of the start condition for start commands during active jobs.
Value
Significance
0x00 (0)
Ignore: Ignore start command
0x01 (1)
Interrupt: Switch immediately to the new job
0x02 (2)
Wait: Start of the new job after Motion Complete
Tab. B.108 PNU 583
PNU 585
Position comparator, min. (Position Comparator, Min.)
Subindex 1
Class: Var
Data type: int32
FW …
Access: rw1
Reading or parameterisation of the lower limit value [SINC] of the position comparator.
Tab. B.109 PNU 585
PNU 586
Position comparator, max. (Position Comparator, Max.)
Subindex 1
Class: Var
Data type: int32
FW …
Access: rw1
Reading or parameterisation of the upper limit value [SINC] of the position comparator.
Tab. B.110 PNU 586