TST
Assembly instructions
FUZ2 -A/-B/-C/-CX/-L
FEIG ELECTRONIC GmbH
Page 52 of 71
FUZ2-A-B-C-CX-L_Montageanleitung_GB
_10.docx
No.
Description
Possible reason for error
F.043
Pre-limit switch fault (light barrier)
• The pre-limit switch for the light barrier remains activated even in the middle end position or upper end position.
F.060
Breakaway recognized
• Breakaway was detected but not fixed
• The automatic lead in after breakaway has failed
F.061
Belt breakage
An input configured as belt breakage sensor (P.50x = 0416) was activated. As long as the display flashes quickly,
movements are not prmitted -> acknowledgment required. Brief foil keyboard stop permits deadman moves.
When the belt break was repaired mechanically and the input is no longer active an automatic acknowledgment is
issued when the deadman closing movement reaches the closed.
F.063
Balance error on loop 3
• disturbing surrounding
• Loop out of tolerance range
F.064
Balance error on loop 4
• disturbing surrounding
• Loop out of tolerance range
F.080
Maintenance is required
• Service counter has expired
F.090
Controller not parameterized
• The min. necessary basic parameters for the controller have not yet been set → Activate DIP-switch and put in
the asked parameters.
F.201
internal E-Stop "mushroom button"
tripped or watchdog (monitoring)
• E-Stop chain was interrupted starting at input „internal E-Stop“ without parameterizing mode having been
selected
• Internal parameter or EEPROM checks defective, pressing the STOP button provides additional information
about the cause.
F.211
External E-Stop 1 tripped
• E-Stop chain was interrupted starting at Input 1
F.212
External E-Stop 2 tripped
• E-Stop chain was interrupted starting at Input 2
F.320
Obstacle during opening
• During opening an obstacle has recognized
F.325
Obstacle during closing
• During closing an obstacle has recognized
F.360
Short circuit detected on edge
input
• Short circuit detected on edges with normally closed contact
• The light beam of the optical edge is interrupted
• Jumper for 1K2 / 8K2 is wrong set
F.361
Number of trips of the Safety input
D, normally this is the integrated
safety edge evaluation, has
reached set limit (configurable in
P.46E)
• Parameterized, maximum number of trips of the safety input D during a door cycle was exceeded → To reset
close the door in deadman mode
• Check the set number of trips in P.46E
F.362
Redundancy error with short circuit
• One of the processing channels for short circuit detection does not react identically with the second channel →
Controller board defective, if no other error message F.3xx is shown
• Dynamical optical safety edge connected but not set in Parameter P.460
F.363
Interruption on edge input
• Connection cable defective or not connected
• Termination resistor incorrect or missing
• Jumper 1K2 / 8K2 incorrectly set