Summary of Contents for Lumina 35

Page 1: ...g...

Page 2: ...duced by Fancom For the latest information about product installation and operation please contact the customer service dept and or the technical service dept of the Fancom concerned In spite of the c...

Page 3: ...trol computer 21 4 System 22 4 1 System 22 4 2 SD Card Menu 24 4 3 Application 25 4 4 Communication 25 4 5 IO Test 27 5 House setup 28 5 1 House setup 28 6 Installer 33 6 1 Ventilation 33 6 2 Heating...

Page 4: ...nual also applies to other control computers in the Fancom F2000 line Always read the safety instructions and warnings carefully before using the control computer Always keep this manual close to the...

Page 5: ...rvice Center Virtually all Fancom equipment can be controlled and managed from a central location This requires the F Central FarmManager software package and a communication module The screens in the...

Page 6: ...mechanical ventilation The fans used with specific ventilation percentages are indicated in the combi table page 7 The control computer supports both natural ventilation and mechanical ventilation The...

Page 7: ...the curtain then switches the fans off The control computer controls how far the curtains open based on the minimum natural inlet settings Transition Natural ventilation Power Tunnel ventilation 2 If...

Page 8: ...let position is equal to the setting Minimum Natural Opening until the inlet position is equal to the setting Maximum Natural Control speed Natural Slow 120 sec Moderate 60 sec Fast 30 sec Example Set...

Page 9: ...controlled by the control computer Controllable fans can be controlled by the control computer via the I O net or via an analog output 0 10V As well as the standard controllable fans up to maximum thr...

Page 10: ...0 m3 M MT phase Exhaust Inlets Ctrl Mod Control lable Extra Relays Inlet Tun Press Pa Cap m3 h 1 2 3 1 2 3 4 5 6 7 8 9 10 M1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 22 250 M2 20 100 0 0 0 0 0 0 0 0 0 0 0 0...

Page 11: ...l computer will only activate the fans when the next position has been reached With falling ventilation the control computer will only deactivate the fans when the lower position has been reached Exam...

Page 12: ...1 1 1 1 1 1 0 0 100 0 180000 T5 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 T6 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 T7 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 T8 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 T9 0 0 0 0 0 0...

Page 13: ...will the modulation percentage Air inlet control depends on the settings The control computer can open the air inlets 30 midway between positions M3 and M4 The inlet position can also be modulated bet...

Page 14: ...that the switch off moment and cycle time can vary Example Optimum modulating control 1 Optimum ON time 2 minutes Maximum cycle time 10 minutes Modulate below 30 Control value ventilation 15 If the c...

Page 15: ...used in combination with variable speed fans of I Fans The setting Modulating below is used to make the setting where the controller switches from variable speed control towards modulating control an...

Page 16: ...temperature must be entered in the curve This may be necessary if floor heating is controlled based on temperature In this case the sensor measures a different temperature to the actual house tempera...

Page 17: ...nuously off if the temperature is equal to or higher than the Setpoint Heating is modulating on if the temperature is in the Hysteresis The control computer calculates the modulation time based on the...

Page 18: ...n use the Max RH limit with evaporative cooling This influence is explained in the user s manual The control computer can use a hysteresis This prevents the cooling being activated or deactivated with...

Page 19: ...n the house drops below Setpoint humidity hysteresis Humidity deactivates when the measured house humidity is equal to or higher than Setpoint humidity A Repeat time can be used to avoid unnecessary a...

Page 20: ...age of animals This means there is a link to the minimum ventilation EARLY 5 means that even at young animals the HumiTemp will react strongly When this factor is NORMAL 10 the reaction is a more gra...

Page 21: ...temperature is lower than setpoint house temperature This means the heating will activate earlier and the difference between the actual and required house temperature will be smaller The control compu...

Page 22: ...etc Never mount the Lumina 35 in a humid and or dusty room and certainly not in the room where the animals are present Mount the Lumina 35 at such a height that you can control the Lumina 35 easily e...

Page 23: ...that the mains voltage and frequency for which this Fancom controller is suitable see chapter Technical Specifications in this manual correspond to the mains voltage and frequency on site Be sure tha...

Page 24: ...lation heating cooling and humidification 4 Clocks registration and external alarms Settings of the clocks input for external registration and outside climate 5 External alarms Setting of external ala...

Page 25: ...ime indication Time and Date Setting of the current time and date Computer name Setting of the name of the control computer Computer number Setting of the sequence number of the control computer in th...

Page 26: ...n When the correct password has been entered all user screens can be accessed The system will request the password again if the controller is not used for a few minutes Change password EditMode Settin...

Page 27: ...his data can be copied back onto the control computer from the SD card This must only be performed by an authorised installer except when backups are made Place the SD card in the SD holder on the FUN...

Page 28: ...and the screen from the SD card onto the control computer Select the required file using the en keys on the alpha numeric keyboard Confirm using the ENTER key The application menu contains the data of...

Page 29: ...ata to zero simultaneously If there is no S2S communication the Receive and Transmit counters should be set to 0 FNet is the Fancom Network Several control computers can be linked via this network FNe...

Page 30: ...est menu inputs can be readout and outputs controlled at system level SYSTEM IO TEST The functions in the IO test menu stop all the control actions of the control computer Only use this to quickly tes...

Page 31: ...ntrol is used This can only be used in combination with RH measurement Measurement outside temp Setting indicating if outside temperature measurement is used If outside temperature measurement is used...

Page 32: ...Ventilation system Setting indicating which ventilation system is used in the house House type Setting indicating which type of ventilation is used in the house Air inlet in use Setting indicating the...

Page 33: ...ration Setting indicating if registration inputs are used Use clocks Setting indicating if clocks are used Light clock Setting indicating if light clocks are used Light relay Setting indicating if lig...

Page 34: ...er amounts based on the number of set up animals Ventilation standard Setting used to determine how the minimum ventilation standard is entered As a percentage irrespective of the number of animals Pe...

Page 35: ...verage house temperature Tiny Small Average Large Huge Max Correctie Setting of the allowed maximum compensation above the average house temperature Tiny Small Average Large Huge HumiTemp Readout of t...

Page 36: ...at these positions must be assigned This prevents ventilation being completely switched off if the user temporarily switches off natural ventilation The screens for the M MT phase are explained below...

Page 37: ...if modulating fans are used INSTALLER VENTILATION COMBI MTT M MT phase min tab page Inlet Position Setting of the ventilation percentage at which fans should activate deactivate and air inlets open cl...

Page 38: ...the ventilation capacity m3 hour for all positions used If ventilation is used in m3 hour animal always fill in this column INSTALLER VENTILATION SETTINGS tab page Miscell Combi control Setting of the...

Page 39: ...the lee side of the house If the wind comes from this direction positions under wind side the ventilation control may be influenced Modulating Setting indicating the required modulation type NONE OPT...

Page 40: ...ON OFF time Modulating Micro control Modulate below Setting of the ventilation percentage below which the control computer will apply modulating control to the linearly controlled part Optimum ON OFF...

Page 41: ...address Setting of the analog output address Analog type Setting indicating the analog control type During mech vent Setting if the air inlet is open or closed during this phase FOLLOW COMBI according...

Page 42: ...tting of the analog output address Analog type Setting indicating the analog control type During mech vent Setting if the air inlet is open or closed during this phase FOLLOW COMBI according to the pe...

Page 43: ...tain at the side of house where the fans are placed must be closed during mechanical ventilation CLOSED UNTIL close until a certain combi step from this step the inlet will follow the combi table Duri...

Page 44: ...address Setting of the analog output address choice LINEAR control or relay output address choice RELAY control Relay type Setting of the type of relay control ON OFF Modulating Analog type Setting i...

Page 45: ...actual house temperature has been above the setpoint house temperature for an uninterrupted period of 2 hours Slope time Setting of the time within which the control computer must complete the requir...

Page 46: ...HOUSE SETUP the clocks to be used have already been entered The data for these clocks can be set here INSTALLER CLOCKS FEED Description Setting of the name of the function Time clock type Setting ind...

Page 47: ...sured by a flow meter Time clock relay Setting of the relay address controlled by the clock Relay type Setting of the passive not controlled relay status N O normally open if it makes no contact N C n...

Page 48: ...ly repeat a certain light pattern For example at the beginning of each hour the lights can be controlled on for 15 minutes then switched off for the other 45 minutes Enter the required time settings i...

Page 49: ...t output Setting of the analog output address used to control the light intensity in percentages Analog type Setting indicating the analog control type Reaction speed Setting of the reaction speed of...

Page 50: ...minute This option is only available if Display AMOUNT only with measurement type CONTACT Display Setting how the unit is displayed AMOUNT number units per minute Amount per min TIME the time the con...

Page 51: ...or via the communication network COMM Only enter the address of the input if INT is selected Input wind speed Setting of the address of the digital input Type wind measure Setting of the type of anem...

Page 52: ...ut Setting the address of the analog input Speed press contr Setting of the speed at which the control computer determines influences SLOW MODERATE FAST Input RH measurement Setting the address of the...

Page 53: ...ut type Setting of the passive not controlled input status N O CONTACT normally open if it makes no contact N C CONTACT normally closed if it makes contact iPRODUCTS to receive alarms from an intellig...

Page 54: ...input or output The address of the chosen connection must be entered at various places in the system settings An input or output address consists of two parts separated by a decimal point NN MM The f...

Page 55: ...ve the following settings Input address The address of the analog input Type Setting of the type of measurement being carried out NONE LEVEL COUNT FREQ DSR feedback Analog outputs have the following s...

Page 56: ...the control voltage of the analog output Digital outputs have the following settings Output address The address of the output Type of channel Shows the type of relay being used NONE ON OFF MODULATING...

Page 57: ...Low level 1 0Vdc Application Counter input min pulse width 25mSec max frequency 20Hz Application Frequency input max frequency 5kHz 5 Digital outputs Relays Relays 1 2 3 make break contact and 4 volta...

Page 58: ...Lumina 35 Technical specifications 55 1 Touch screen 2 HI mainboard 3 SBC 4 LED strip 5 FUNC CPU 6 IOB 4 I O 7 FPD25 Power supply 8 FRM 8 Internal relay...

Page 59: ...nical specifications 56 AI type Type analog input Voltage measurement U Resistance measurement R AO 4 Analog outputs AI 4 Analog inputs DI 4 Digital inputs Relay 4 Digital outputs relays DO 8 Extra di...

Page 60: ...or Example Setting the I O net terminal resistor 1 One control computer connected to two I 0 network modules using one I O net The control computer is located between the two I O network modules This...

Page 61: ...lace Panningen the Netherlands Hereby declares that Lumina 35 Satisfies the conditions of 1 The Low Voltage Directive 2014 35 EU according to EN 61010 2 the EMC Guideline directive 2014 30 EU Emission...