4.1.8 Pressure transmitter
Service menu
Pressure transmitter
Description
Calibration of pressure transmitters
Zero-calibrate all pressure transmitters in the air han-
dling unit.
Submenu
Submenu
Select type 0 calibration
● Set zero calibration: [Manual/Auto]
If Auto is selected, zero calibration is carried out auto-
matically every time the unit stops.
Start zero-calibration
Confirm to start zero calibration, or press Esc to abort.
During zero calibration the unit will stop for about 5 min.
5 min.
Zero calibration is being performed
Acknowledgement that zero calibration is in progress/is
complete.
3005858-2017-09-28
Service level
45/52