Service menu
Damper
Description
Shown only in case of
modulating damper
motor
Shown only if modula-
ted recirculation is con-
figured
Exhaust air damper, status
● Current damper position: [%]
● Current supply air [m3/h] [l/s]
Recirculation damper
Recirculation damper, status
● Current damper position: Open/closed
● Current supply air [m3/h] [l/s]
Shown at Belimo Mod-
bus damper motor
Damper motor, Modbus
● Current damper setting [%]
● Absolute position [Feedback]
● Test run: Yes/No
● Communication [Active] / [Inactive]
Shown only in case of
modulating damper
motor
Set recirculation damper
● Current damper setting [%]
● Set correction factor
● Set offset [V]
● Current supply air [m3/h] [l/s]
Shown only if modula-
ted recirculation is con-
figured
Set I-time for modulated recirculation
● P-band VOC/CO2 [ppm]
● Set I-time VOC/CO2 [sec]
● Set I-time temperature [s]
Shown only if modula-
ted recirculation is con-
figured
Set gain factor for modulated recirculation
● Set gain factor
Smoke-evacuation damper
Damper motor, Modbus
● Current damper setting [%]
● Absolute position [Feedback]
● Test run: Yes/No
● Communication: Active / Inactive
Override smoke-evacuation damper
● Current damper setting [%]
● Set remaining time until overriding terminates
[hh:mm:ss]
● Override: On/ Off
3005858-2017-09-28
Service level
43/52