3.1.2 Temperature
Installer menu
Temperature
Description
TEMPERATURE
Setting of temperature regulation type, cooling and au-
tomatic functions.
Submenu
Any comments
Shown if
Outdoor air
temperature (external
sensor)
is configured
External outdoor temperature sensor
● Switch on/off external outdoor temperature sensor
Shows current operating temperatures
● Outdoor temperature [°C]
● Exhaust air [˚C] if installed
● Extract air [˚C] if installed
● Supply air [˚C]
● Current regulation form
Shown only when room operation is installed.
Symbols which are only shown when Summer/Winter
changeover is activated:
Shown only when the unit is in summer operation.
Shown only when the unit is in winter operation.
Set temperature setpoint
● Max. supply air temperature [°C]
● Temperature setpoint [°C]
● Min. supply air temperature [°C]
Max. and min. are
not
shown when constant supply air
temperature is selected.
● Calibrate room temperature measurement = Set-
ting of sensor offset on room sensor.
Shown only if cooling is
installed
Minimum input air for cooling requirement
● Min. supply air temperature [˚C]
Set temperature regulation form
● Constant supply air
● Constant extract air
● Constant room
● Constant supply/extract air difference
Summer/winter compensation
● On/Off Summer/winter compensation
3005858-2017-09-28
Installer level
15/52