4.1.4 Heating recovery
Service menu
Heating recovery
Description
HEATING RECOVERY
Show current operating status. Set functions and forced
fan control of heat exchanger.
Submenu
Submenu/Any com-
ments
Crossflow heat exchanger
Shows current status of crossflow heat exchanger
● Current outdoor temperature [°C]
● Current exhaust air temperature [°C]
● Current recovery signal [%]
● Current extract air temperature [°C]
● Current supply air temperature [°C]
● Current heating recovery [%]
Forced control of crossflow heat exchanger
Forced operation is only possible once the unit has
started.
● Set remaining time until forced operation termi-
nates [hh:mm:ss]
● Activate forced operation: On/ Off
● Set forced operation setpoint [%]
● Current extract air temperature [°C]
● Current supply air temperature [°C]
● Current heat recovery [%]
Efficiency crossflow heat exchanger
● Current efficiency [%]
● Correction factor [%]
● Alarm in case of low efficiency: Yes/No
● Alarm level [%]
Shown at Belimo Mod-
bus damper
Bypass damper, Modbus
● Current damper setting [%]
● Absolute position [Feedback]
● Test run: Yes/No
● Communication: Active / Inactive
Shown for tempera-
ture-controlled ice pro-
tection
Set ice-protection of crossflow heat exchanger
● Set ice protection temperature [°C]
● Set ice protection P band. [°C]
● Shows current exhaust air temperature [°C]
● Ice protection in progress: Yes/No
Shown for tempera-
ture-controlled ice pro-
tection
Show status of crossflow heat exchanger
● Shows current exhaust air temperature [°C]
● Protection in progress: Yes/No
3005858-2017-09-28
Service level
35/52