4.1.1 Fan
Service menu
Fan
Description
FAN
Show current operating status. Set functions and forced
fan control.
Submenu
Any comments
Set fan operation
●
SERVICE
● Manual
STOP
● Constant
LOW
speed
● Constant
HIGH
speed
● Automatic operation according to
weekly program
NB!
When setting
SERVICE
, the unit cannot be started
from the WEB user interface, but only from the hand-
held terminal.
Supply air fan operating status
● Current setpoint [%]
● Specific Fan Power SFP [J/m3]
● Current power consumption [W]
● Current rpm [RPM]
● Current ventilation [m3/h] [l/s] [Pa]
● Current k-factor for calculating airflow
Symbol
is shown when an alarm from the frequency
converter is triggered.
Forced control of supply air fan and setting of K
factor.
Forced operation is only possible once the unit has
startet.
● Set the forced control setpoint [%]
● Setting of remaining time until forced control ex-
pires [hh:mm:ss]
● Activate forced control: On/Off
● Current rpm [RPM]
● Current ventilation [m3/h] [l/s] [Pa]
● Setting of k-factor
Symbol
is shown when an alarm from the frequency
converter is triggered.
Extract air fan operating status
● Current setpoint [%]
● Specific Fan Power SFP [J/m3]
● Current power consumption [W]
● Current rpm [RPM]
● Current ventilation [m3/h] [l/s] [Pa]
● Current k-factor for calculating airflow
Symbol
is shown when an alarm from the frequency
converter is triggered.
3005858-2017-09-28
Service level
25/52