Installation and Startup Guide

 

This document covers the installation of MT8102iE Series HMI, for the detailed specifications and 
operation, please refer to Brochure and EasyBuilder Pro User Manual. 

Install Environment: 

NEMA Rating

 

The 

HMI product is NEMA 4 rated (Indoor Only). 

 

Electrical 
Environment

 

The 

HMI product has been tested to conform to European CE requirements. This 

means that the circuitry is designed to resist the effects of electrical noise. This 
does not guarantee noise immunity in severe cases. Proper wire routing and 
grounding will insure proper operation.

 

Environmental 
Considerations

 

(1)  Make sure that the displays are installed correctly and that the operating 

limits are followed. Avoid installing units in environments where severe 
mechanical vibration or shocks are present. 

(2) 

Do not operate the unit in areas subject to explosion hazards due to 
flammable gases, vapors or dusts.

 

(3)  Do not install the unit where acid gas, such as SO2 exists. 

(4) 

This device should be mounted in the vertical position and for use on the flat 
surface enclosure.

 

(5) 

Conform to UL508 (ISBN 0-7629-0404-6) machine safety for use in 
Pollution Degree 2 Environment.

 

 

Unpacking the Unit

 

Unpack and check the delivery. If damage is found,   
notify the supplier.

   

 

Installation Instructions 

Secure the operator panel in position, using all the fastening holes and the provided brackets   
and screws. Screw Torque: 2.6 ~ 3.9 lbf.in. (For reaching waterproof effect and preventing the panel 
from being deformed.) 
 

 

 

 

Type 

A(mm) 

B(mm) 

MT8102iE 

260 

202 

 

USB Stick Clamp Usage 

Combining the USB Stick with the clamp and the tying strap can prevent USB stick from disconnecting 
with HMI when strong vibration is present. 
1. Insert the USB connector to the clamp and tie them together with the tying strap. 
2. Press the spring and insert the USB stick into HMI. 

 

Power Connections 

 

 

 

 

 

System Settings 

When HMI is powered up and displays image,   
click the system setting button. 
(Default System Password: 111111) 
It is necessary to connect the HMI to   
your network through a RJ-45 cable. 
 
 
 
 

 

MT8102iE series

 

                                                                                                               

Installation Instruction 

 

NOTE:   

Place the operator panel on a stable 
surface during installation. Dropping it or 
letting it fall may cause damage. 

 

Go to the Network tab, you may choose 
to auto get DHCP IP, or designate your 
own IP.

 

NOTE:   

1. Conne

ct positive DC line to the ‘+’ terminal and 

the DC 

ground to the ‘-’ terminal. 

2. When using a USB cable to download project 
file, please do not connect HMI with PLC and PC 
simultaneously to prevent potential difference from 
destroying USB ports of HMI and PC. 

(A) 

(B) 

Cutout 

(1) Installation Instruction, 2-sided A4 *1 

(2) Human Machine Interface *1 

 

(3) Power Connector *1 

 

(4) Brackets & Screws *1 pack 

(5) USB Stick Clamp & Tying Strap *1

 

(6) Fuse 1.25A/250V 5*20mm *1

 