Service menu
Heating
Description
Shown for the electric
heating coil 1
Forced control of electric heating coil
Forced operation is only possible once the unit has
started.
● Set forced operation setpoint [%]
● Set remaining time until forced operation termi-
nates [hh:mm:ss]
● Activate forced operation: On/Off
● Current signal at heating output [V]
● Current status Heating relay 1: Open/closed
● Current status Heating relay 2: Open/closed
Shown for the electric
heating coil 1
Set min airflow for partially connected electric heat-
ing coil 1
● Set supply airflow [m3/h] [l/s]
Reduced
is displayed if the heating output is reduced
due to low airflow.
Shown for the electric
heating coil 1
Set min airflow for 100% connected electric heating
coil 1
● Set supply airflow [m3/h] [l/s]
Reduced
is displayed if the heating output is reduced
due to low airflow.
Shown for the electric
heating coil 2
Show current operating status. Set regulation for
current type of electric heating coil 2.
● Current heating [%]
● Set regulation form:
● 0–10 V
● 1 step
● 2 step
● 3 step
● 4 step
● 5 step
● 7-step binary
● Overheating: Low/High
● Current signal at heating output [V]
● Current status Heating relay 21: Open/closed
● Current status Heating relay 22: Open/closed
Shown for the electric
heating coil 2
Current status electric heating coil 2
● Current status Heating relay 21: Open/closed
● Current status Heating relay 22: Open/closed
● Current status Heating relay 23: Open/closed
● Current status Heating relay 24: Open/closed
● Current status Heating relay 25: Open/closed
● Current status Heating relay 26: Open/closed
3005858-2017-09-28
Service level
31/52