Installer menu
Store functions
Description
Shown only if reg. type
Standard
is selected.
Select Heat 1 regulation type
Select
Standard
if
Heat1
is to be regulated as a single
heating surface.
Shown only if reg. type
Splitter
is selected.
Select Heat 1 regulation type
Select
Splitter
if Heat1 is to be regulated as 2 heating
surfaces connected in sequence =
Heat1
and
Heat12
● Set exit signal
Heat 12
[0-10V/2-10V]
● Read off current exit signal for
Heat 12
[V]
Shown only if reg. type
Splitter
is selected.
Set reg. parameters for exit Heat 12
● Mark to activate the function
● Set delay for condenser [s]
● Read off current condenser delay [s]
Shown only if reg. type
Splitter
is selected.
Set reg. parameters for exit Heat 12
● Set min active time for
Heat 12
● Read off current active time for
Heat 12
● Mark for activation of rise/fall time
● Set min rise/fall time [Sec]
Shown only if reg. type
Splitter
is selected.
Set reg. parameters for exit Heat 12
● Mark to activate hysteresis
Heat 1
● Set hysteresis for relay
Heat 1
[%]
Shown only if reg. type
Splitter
is selected.
Set reg. parameters for exit Heat 1
● Mark to deactivate
Heat 1
Shown only if reg. type
Copy
is selected.
Select Heat 1 regulation type
Select
Copy
if
Heat 1
is to be regulated as 2 heat sur-
faces connected in parallel.
Set limits for Heat 2
In many cases
Heat2
is an electrically heated surface.
To save energy from this heat source, the control sys-
tem may be set to automatically reduce use of this heat
source, depending on the deviation from room tempera-
ture or depending on outdoor temperature.
Set limits for Heat 2
● None - no limits for
Heat 2
Shown only for
Room
temperature
limitation
Room temperature limits
● Set temperature difference (setpoint/current) [°C]
● Connection degree per step [%]
● Read of Temperature (setpoint/current) [°C]
3005858-2017-09-28
Installer level
22/52