Alarm no
Alarm type
Alarm delay secs
Alarm limit
Auto reset
Machine stop
Alarm text - Handheld terminal
129
B
3
N/A
Supply air EC Contrl. : Loss of supply phase
130
B
3
N/A
Extract air EC Contrl. Loss of supply phase
131
A
3
N/A
X
X
FanIO 1 (Air2FanIO21): No communication
132
A
3
N/A
X
X
FanIO 2 (Air2FanIO21): No communication
133
A
3
N/A
X
X
Damper motor (supply air), ID 130: No communication
134
A
3
N/A
X
X
Damper motor (exhaust air), ID 131: No communication
135
A
3
N/A
X
X
Damper motor (recirculation), ID 132: No communication
136
A
3
N/A
X
X
Damper motor (heat exchanger), ID 133: No communication
137
A
3
N/A
X
X
Damper motor (drying damper), ID 134: No communication
141
A
3
N/A
X
X
Valve motor (Heating), ID 138: No communication
142
A
3
N/A
X
X
Valve motor (cooling), ID 139: No communication
143
A
3
N/A
X
X
Valve motor (Heating2), ID 140: No communication
144
A
3
N/A
X
X
Valve motor (Heat recovery unit), ID 141: No communication
145
A
3
N/A
X
X
Valve motor (pre-heating), ID 142: No communication
146
A
3
N/A
X
X
Valve motor (6), ID 143: No communication
149
B
10
N/A
X
Damper motor (supply air): Unable to reach setpoint
150
B
10
N/A
X
Damper motor (exhaust air): Unable to reach setpoint
151
B
10
N/A
X
Damper motor (recirculation): Unable to reach setpoint
152
B
10
N/A
X
Damper motor (heat exchanger): Unable to reach setpoint
153
B
10
N/A
X
Damper motor (drying damper): Unable to reach setpoint
157
B
10
N/A
X
Valve motor (Heating): Unable to reach setpoint
158
B
10
N/A
X
Valve motor (cooling): Unable to reach setpoint
159
B
10
N/A
X
Valve motor (heating 2): Unable to reach setpoint
160
B
10
N/A
X
Valve motor (Heat recovery unit): Unable to reach setpoint
161
B
10
N/A
X
Valve motor (pre-heating): Unable to reach setpoint
162
B
10
N/A
X
Valve motor (6): Unable to reach setpoint
166
B
360
N/A
Fire damper not closed
167
B
360
N/A
Fire damper not open
168
B
300
N/A
X
Heating 2 cut out due to low airflow
169
B
30
N/A
Electric heating coil 2: overheating alarm
170
B
30
N/A
Contactor for electric heating coil 2 is stuck
171
A
10
N/A
X
X
Temperature sensor error: Water heating coil 2
172
A
10
N/A
X
Pump alarm: Water heating coil 2
173
A
3
N/A
X
Frost alarm: Water heating coil 2
174
A
10
N/A
X
X
Temperature sensor error: combi-coil
175
A
10
N/A
X
Pump alarm: Combi-coil
176
A
3
N/A
X
Frost alarm: Combi interface (heating)
177
A
3
N/A
X
Frost alarm: Combi interface (cooling)
178
B
10
N/A
Alarm from heat exchanger or circulation pump