Installer menu
Fan operation
Description
Select fan regulation form
● Constant pressure P [Pa]
● Constant airflow [m
3
/h] / [l/s]
● Extract air slave [Pa] & [m
3
/h] [l/s]
● Supply air slave [Pa] & [m
3
/h] [l/s]
● Constant VOC/CO
2
[ppm CO
2
]
● Fan optimiser [m
3
/h] [l/s]
● Fan optimiser slave [%] & [m
3
/h] [l/s]
● Constant motor speed [%]
Shown for
modulated
circulating air /
VOC/CO
2
intermittent
circulating air
Set fan regulation
● Set point for max VOC/CO
2
[ppm]
● Setpoint for min. VOC/CO
2
[ppm]*
● Setpoint for minimum outdoor air [%]
● Recirculation air VOC/CO2: On/Off
* Shown only if
VOC/CO
2
intermittent circulating air
is selected
Read-out of pressure transmitter Modbus address-
es
● Extract air = PTH-6202 SwX
● Supply air = PTH-6202 SwY
Shown for regulation
modes:
● Fan Optimiser
Override supply air
● Fire: Yes/No
● Cooling: Yes/No
● Summer night cooling: Yes/No
Shown for regulation
modes:
● Fan Optimiser
● Fan optimiser
slave
Override exit air
● Fire: Yes/No
● Cooling: Yes/No
● Summer night cooling: Yes/No
Set fan compensation
● Outdoor temperature compensation: On/ Off
Shown only if outdoor
temperature compen-
sation is:
On
Set outside temperature compensation
● Max setpoint reduction [%]
● Outdoor temperature for full compensation [˚C]
● Outdoor temperature for start of compensation [˚C]
3005858-2017-09-28
Installer level
13/52