Installer menu
Store functions
Description
Shown only in case of
"outdoor tempera-
ture"
limits
Outdoor temperature limits
● Set connection level [°C]
● Read off current outdoor temperature [°C]
Delayed start-up Heat 2
● Mark to activate the function
● Set delayed start
Heat 2
[Sec.]
● Read off current time in delayed start [Sec]
Set cooling limits
Limit cooling in case of high room temperature
The function is set to block connection of cooling even
though there is an active cooling requirement.
● Mark to activate the function
● Set setpoint for stop of cooling [°C]
If the current room temperature exceeds this setpoint,
cooling will be blocked.
Blocking of cooling
This function is used to limit cooling with fresh air.
● Mark to activate the function
● Set free cooling stop setpoint [°C]
Cold recovery
● Mark to activate the function
The function is meant to ensure that when there is a
cooling requirement and the outdoor temperature is
+1˚C > room temperature, the unit damper will be diver-
ted to minimum fresh air to save cooling energy.
3005858-2017-09-28
Installer level
23/52