4.1.7 Temperature sensor correction
Service menu
Temperature sensor correction
Description
Settings for sensor correction/calibration
For correction of measurement errors, cable resistance
and sensor tolerances.
Submenu
Any comments
Shown if
heating coil
1
is configured
Calibrate temperature measurement - Heating coil 1
Set sensor offset [+/-3.5°C]
● Shows current sensor temperature [°C]
● Set calibration value [°C]
Shown if
heating coil
2
is configured
Calibrate temperature measurement - Heating coil 2
Set sensor offset [+/-3.5°C]
● Shows current sensor temperature [°C]
● Set calibration value [°C]
Shown if
water cool-
ing
is configured
Calibrates temperature measurement - Water cool-
ing
Set sensor offset [+/-3.5°C]
● Shows current sensor temperature [°C]
● Set calibration value [°C]
Shown if
outdoor sen-
sor
is configured
Calibrates temperature measurement - outdoor tem-
perature sensor
Set sensor offset [+/-3.5°C]
● Shows current sensor temperature [°C]
● Set calibration value [°C]
Up to 4
additional
sensors
can be config-
ured
Calibrates temperature measurement - Addition
sensor
Set sensor offset [+/-3.5°C]
● Shows current sensor temperature [°C]
● Set calibration value [°C]
3005858-2017-09-28
Service level
44/52
Summary of Contents for EXcon
Page 52: ......