MCOCW Control
Device
Fault code
Category
Alarm description
Troubleshooting
(See appendix 1: "Simplified diagrams" for the positioning of dampers,
sensors, air directions, etc.)
xx yy
z
49 01
1
Module configured in-
correctly. Check CN6
on circuit board
● Check the jumper in the CN6 connector on the MCOCW mod-
ule. There must be a jumper across 5 and 6.
49 02
1
Fan speed temporarily
reduced
Fan speed temporarily reduced because warning limit for frost pro-
tection of water heating coil has been reached.
49 03
1
VEX temporarily stop-
ped
Fan speed temporarily reduced because stop temperature for frost
protection of water heating coil has been reached
49 04
1
VEX stopped
MCOCW is temporarily controlled by the Lodam Multi Tool.
49 06
1
Heat control currently
run locally due to serv-
ice
MCOCW temporarily controlled by Lodam Multi Tool. Override
lasts for max. 60 minutes.
49 07
1
Heat control safety
functions overridden lo-
cally due to service
MCOCW temporarily controlled by Lodam Multi Tool. Override
lasts for max. 60 minutes.
49 11
2
Heating has been
blocked due to cold
water in the feed pipe
EXact has detected a heating requirement, but via TE-SPT has
registered cold water in the feed pipe. Heating is therefore blocked
for 6 hours.
● Check that there is hot water in the feed pipe if the heating
function is required.
49 12
2
Cooling has been
blocked due to hot wa-
ter in the feed pipe
EXact has detected a cooling requirement, but via TE-SPT has
registered hot water in the feed pipe. Cooling is therefore blocked
for 6 hours.
● Check that there is cold water in the feed pipe if the cooling
function is required.
49 13
4
Heat control detected
which was not selected
in VEX/CX configura-
tion
The heating coil is configured as MCOCW in menu 3.4 "Accesso-
ries".
49 14
4
Heat control configured
incorrectly in connec-
tion with selected
VEX/CX configuration
● Check the jumper in the CN6 connector on the MCOCW mod-
ule. There must be a jumper across 5 and 6.
49 15
4
No modbus communi-
cation to water heat
control
● Check the modbus cable between the connection board (EX-
act)/main board (EXact2) and the MCOCW module.
● Check the modbus cable from the MCOCW module to the oth-
er units for faulty wiring.
3005167-2022-02-02
Alarms
99/108