Airflow/pressure
Unit
Fault code
Category
Alarm description
Troubleshooting
(See appendix 1: "Simplified diagrams" for the location of dampers, sen-
sors, air directions, etc.)
xx yy
z
20 01
1
Airflow/pressure in ex-
tract air duct airflow too
high
The unit provides airflow that is 25% above the setpoint.
● Check the fan speed settings in indoor air quality level and the
fan limits.
20 02
2
Airflow/pressure in ex-
tract air duct has been
too high for last 30 mi-
nutes.
The unit has provided an airflow/pressure that is 25% above the
setpoint for more than 30 minutes.
● Check the fan speed settings in indoor air quality level and the
fan limits.
20 03
1
Airflow/pressure in ex-
tract air duct too low
The unit is providing an airflow/pressure that is 25% below the set-
point.
● Check the fan speed settings in indoor air quality level and the
fan limits.
20 04
2
Airflow/pressure in ex-
tract air duct has been
too low for last 30 mi-
nutes
The unit has provided airflow/pressure that is 25 % below the set-
point for more than 30 minutes.
● Check the fan speed settings in indoor air quality level and the
fan limits.
20 05
1
Airflow/pressure in
supply air duct too high
The unit provides airflow that is 25% above the setpoint.
● Check the fan speed settings in indoor air quality level and the
fan limits.
20 06
2
Airflow/pressure in
supply air duct has
been too high for last
30 minutes
The unit has provided an airflow/pressure that is 25% above the
setpoint for more than 30 minutes.
● Check the fan speed settings in indoor air quality level and the
fan limits.
20 07
1
Airflow/pressure in
supply air duct too low
The unit is providing an airflow/pressure that is 25% below the set-
point.
● Check the fan speed settings in indoor air quality level and the
fan limits.
20 08
2
Airflow/pressure in
supply air duct has
been too low for last 30
minutes
The unit has provided airflow/pressure that is 25 % below the set-
point for more than 30 minutes.
● Check the fan speed settings in indoor air quality level and the
fan limits.
20 09
1
Minimum airflow for
cooling/heating units in
the supply air duct was
not achieved
The required supply airflow for operating cooling/heating units was
not achieved.
● Check the fan speed settings in indoor air quality level and the
fan limits.
20 10
3
Minimum airflow for
cooling/heating units in
the supply air duct has
not been achieved for
last 30 minutes
The required supply airflow for operating cooling/heating units was
not achieved within 30 minutes.
● Check the fan speed settings in indoor air quality level and the
fan limits.
20 11
1
Cooling cannot be re-
leased because sup-
ply/extract airflow ratio
was not achieved
The required air balance between supply air and extract air is high-
er than the permitted limit of 1. 15:1
● Check the fan speed settings in indoor air quality level and the
fan limits.