HC Alarm
Unit
Fault code
Category
Alarm description
Troubleshooting
(See appendix 1: "Simplified diagrams" for the location of dampers, sen-
sors, air directions, etc.)
xx yy
z
14 10
3
Return water temp. too
low. Frost protection
activated. VEX tempo-
rarily stopped
HCW:
● Check that the hot water supply to the heating coil is function-
ing.
If the hot water supply is functioning, check if the motor valve
opens and the circulation pump is running.
● Check by turning the unit to "OFF" in the user menu and force
start the motor valve and circulation pump in specialist menu
8.3.
The alarm resets automatically when the temperature rises above
the heat retention level.
14 11
3
Return water temp.
measured by external
sensor becoming too
low. VEX running in re-
duced mode
HCW:
● Check that the hot water supply to the heating coil is function-
ing.
If the hot water supply is functioning, check if the motor valve
opens and the circulation pump is running.
● Check by turning the unit to "OFF" in the user menu and force
start the motor valve and circulation pump in specialist menu
8.3.
The alarm resets automatically when the temperature rises above
the heat retention level.
14 12
3
Return water temp.
measured by external
sensor becoming too
low. VEX temporarily
stopped.
HCW:
● Check that the hot water supply to the heating coil is function-
ing.
If the hot water supply is functioning, check if the motor valve
opens and the circulation pump is running.
● Check by turning the unit to "OFF" in the user menu and force
start the motor valve and circulation pump in specialist menu
8.3.
The alarm resets automatically when the temperature rises above
the heat retention level.
14 13
4
Max. total no. of re-
starts within one hour
reached.
HCW:
● Check that the hot water supply to the heating coil is function-
ing.
If the hot water supply is functioning, check if the motor valve
opens and the circulation pump is running.
● Check by turning the unit to "OFF" in the user menu and force
start the motor valve and circulation pump in specialist menu
8.3.
The alarm resets automatically when the temperature rises above
the heat retention level.
3005167-2022-02-02
Alarms
76/108
Summary of Contents for EXact2 VEX240 series
Page 105: ...3005167 2022 02 02 105 108...
Page 106: ...3005167 2022 02 02 106 108...
Page 107: ...3005167 2022 02 02 107 108...
Page 108: ......