Summertime compensation (menu 3.1.2.2)
Function
The room temperature can be raised if outdoor air temperatures are high.
NB:
Summertime compensation is active only if room temperature regulation is activa-
ted for the indoor air quality level in Menu 3.1.1 (Operation settings -> Temp. reg. -
> Room).
Selecting summer-
time compensation
Activate in Menu 3.1.3.2.
Summertime com-
pensation
Summertime compensation raises the room temperature when the temperature
outside is high, to reduce the temperature difference people experience when en-
tering and exiting the building. The result is that indoor air quality feels comforta-
ble even when people are wearing summer clothing. If summertime compensation
is required, select values as indicated below.
Example
Room temperature is
Action
Too cold when outdoor air tempera-
ture high
'Temp. high' lowered and/or "Comp.
grad' raised
Too warm when outdoor air tempera-
ture high
'Temp. high' raised and/or "Comp. grad'
lowered
Menu 3.1.4 + Menu 8.1 - Filter (monitoring in case of pressure)
General
The pressure across outdoor air and extract air filters is monitored by sensors
close to the filters. A soiled filter will generate a warning signal, and then an alarm
signal, to indicate that it needs replacing.
3.1.4 Filter
Current pressure:
Outdoor air
Extract air
Warning:
Outdoor air >
Extract air >
Alarm:
0 Pa
0 Pa
185 Pa
185 Pa
Outdoor air >
Extract air >
200 Pa
200 Pa
3005167-2022-02-02
Starting up the unit for operation
41/108