Cooling unit
Unit
Fault code
Category
Alarm description
Troubleshooting
(See appendix 1: "Simplified diagrams" for the positioning of dampers,
sensors, air directions, etc.)
xx yy
z
25 08
3
Outdoor air duct tem-
perature sensor short-
circuited
● Check the sensor's resistance complies with the actual tem-
perature. See temperature resistance table appendix 2.
● If the sensor resistance has significantly changed in value, it
should be replaced.
25 15
3
Cooling control detec-
ted but not selected in
VEX configuration
The cooling unit is configured in Menu 3.3 VEX configuration
25 16
3
No modbus communi-
cation to cooling con-
trol
● Check the modbus cable between the connection board and
the MCUC module.
● Check the modbus cable from the MCUC module to the other
units for faulty wiring
External cooling unit (MXCU) sensor
Unit
Fault code
Category
Alarm description
Troubleshooting
(See appendix 1: "Simplified diagrams" for the location of dampers, sen-
sors, air directions, etc.)
xx yy
z
27 01
4
Supply air duct temper-
ature sensor discon-
nected
● Check the sensor's resistance complies with the actual tem-
perature. See temperature resistance table appendix 2.
● If the sensor resistance has significantly changed in value, it
should be replaced.
27 02
4
Supply air duct temper-
ature sensor short-
circuited
● Check the sensor's resistance complies with the actual tem-
perature. See temperature resistance table appendix 2.
● If the sensor resistance has significantly changed in value, it
should be replaced.
3005167-2022-02-02
Alarms
85/108