Menu 3.4 - Accessories
Ice-detect.
De-icing method
Heating coil >
Cooling unit >
Power step HCE >
Filter detect. >
PIR >
TS >
CO2 >
RH >
Dining solution
AUX OUT setting >
ALC >
3.4 Accessories
Pressure
0
MHCE
None
4
Timer
PIR1
TS Room
MIOCO2
None
No
1
Line in menu 3.4
Factory-set and
should not be
changed.
Remarks:
Ice detection method
Should only be changed when
ice-detection sensors are ret-
rofitted.
Options:
● Pressure
● Tice
De-icing method
Select de-icing method (meth-
od no.) for de-icing of heat ex-
changer. See section on de-
icing on following pages,
where the VEX type and asso-
ciated de-icing methods are
described.
Heating unit
Options:
● IHCW (set at the factory
for the the EXact2 main
board, if the VEX was
purchased with HCW)
● MHCE (Electric heating
coil)
● MHCW (Water heating
coil),
● None
Cooling unit
Options:
● CH
● CU (cooling unit from EX-
HAUSTO)
● CCW (cold water coil)
● MXCU (external cooling
unit)
● None
Filter detection
x
Should only be changed when
sensors for detecting filter soil-
ing are retrofitted. Options:
● Pressure
● Hours
Power rating step
HCE
This menu item is only active if
MHCE is selected (Can only
be active for VEX340-50-60).
3005167-2022-02-02
Starting up the unit for operation
18/108