ALC extract air damper alarm
Unit
Fault code
Category
Alarm description
Troubleshooting
(See appendix 1: "Simplified diagrams" for the location of dampers, sen-
sors, air directions, etc.)
xx yy
z
52 01
4
MD1: No communica-
tion to damper motor.
● Check Modbus cable to and from ALC damper for faulty
mounting.
52 02
4
MD1: Incorrect type of
damper motor.
● Check that the damper motor type and Modbus address (17)
are correct.
52 03
1
MD1: Damper motor
cannot move.
● Check whether ALC dampers have reduced mobility (are
blocked).
ALC alarm
Unit
Fault code
Category
Alarm description
Troubleshooting
(See appendix 1: "Simplified diagrams" for the location of dampers, sen-
sors, air directions, etc.)
xx yy
z
54 01
2
Increased rotation
leakage
Leakage pressure (diff. pressure) is below 0 Pa. The ALC damper
cannot compensate for the pressure conditions.
● If necessary, contact support.
54 02
2
Diff pressure below 0
Pa for more than 5
min. Leakage may oc-
cur.
The unit continues, but there is a risk of leakage.
● Check whether the ALC damper in the extract air is blocked.
54 03
2
Excessive damper ac-
tivity/intermittent fluctu-
ations
The unit continues, but there is a risk of the damper motor suffer-
ing overload
● If necessary, contact support.