Frequency converter 2
Unit
Fault code
Category
Alarm description
Troubleshooting
(See appendix 1: "Simplified diagrams" for the positioning of dampers,
sensors, air directions, etc.)
xx yy
z
02 15
4
Frequency converter
hardware fault
Fault on frequency converter 2.
02 16
4
Frequency converter
software version out of
date
● Upgrade software in frequency converter 2.
Rotor control
Unit
Fault code
Category
Alarm description
Troubleshooting
(See appendix 1: "Simplified diagrams" for the positioning of dampers,
sensors, air directions, etc.)
xx yy
z
03 01
3
Rotation alarm
● Check drive belt is intact. Faulty drive belts must be replaced
by a service technician.
● Check the rotor can rotate easily
● Check for defective rotor guard
03 02
3
Low voltage alarm
● Check for rotor control low voltage at the supply terminals in
the control system box
03 03
3
Overvoltage alarm
● Check for rotor control over voltage at the supply terminals in
the control system box
03 04
3
Rotor motor drawing
too much current
Alarm indicates the step motor (most likely) or rotor control is de-
fective
● Check parts and replace defective part
03 05
3
Rotor control overhea-
ted
Temperature in the rotor control has risen above 95°C
● Replace rotor control
03 06
3
No modbus communi-
cation to rotor control
● Check the cable between the connection board and rotor con-
trol
03 07
4
Rotor control inopera-
tive and outdoor air
temperature below 3°C
The VEX has stopped because the outdoor air temperature is be-
low 3°C and the rotor does not operate.
3005167-2022-02-02
Alarms
67/108