HC Sensor
Device
Fault code
Category
Alarm description
Troubleshooting
(See appendix 1: "Simplified diagrams" for the positioning of dampers,
sensors, air directions, etc.)
xx yy
z
15 01
4
Supply air duct temper-
ature sensor discon-
nected
● Check the sensor's resistance complies with the actual tem-
perature. See temperature resistance table appendix 2.
● If the sensor resistance has significantly changed in value, it
should be replaced.
15 02
4
Supply air duct temper-
ature sensor short-
circuited
● Check the sensor's resistance complies with the actual tem-
perature. See temperature resistance table appendix 2.
● If the sensor resistance has significantly changed in value, it
should be replaced.
15 05
4
Supply water pipe tem-
perature sensor on wa-
ter cooling coil discon-
nected
● Check the sensor's resistance complies with the actual tem-
perature. See temperature resistance table appendix 2.
● If the sensor resistance has significantly changed in value, it
should be replaced.
15 06
4
Supply water pipe tem-
perature sensor on wa-
ter cooling coil short-
circuited
● Check the sensor's resistance complies with the actual tem-
perature. See temperature resistance table appendix 2.
● If the sensor resistance has significantly changed in value, it
should be replaced.
15 07
4
Return water pipe tem-
perature sensor on wa-
ter heating coil discon-
nected
● Check the sensor's resistance complies with the actual tem-
perature. See temperature resistance table appendix 2.
● If the sensor resistance has significantly changed in value, it
should be replaced.
15 08
4
Return water pipe tem-
perature sensor on wa-
ter heating coil short-
circuited
● Check the sensor's resistance complies with the actual tem-
perature. See temperature resistance table appendix 2.
● If the sensor resistance has significantly changed in value, it
should be replaced.
15 09
4
Return water pipe ex-
ternal temperature sen-
sor on water heating
coil disconnected
● Check the sensor's resistance complies with the actual tem-
perature. See temperature resistance table appendix 2.
● If the sensor resistance has significantly changed in value, it
should be replaced.
15 10
4
Return water pipe ex-
ternal temperature sen-
sor on water heating
coil is short-circuited
● Check the sensor's resistance complies with the actual tem-
perature. See temperature resistance table appendix 2.
● If the sensor resistance has significantly changed in value, it
should be replaced.
15 13
4
Heat control internal
temperature sensor
disconnected
● Replace the heat control circuit board MHCW
15 14
4
Heat control internal
temperature sensor
short-circuited
● Replace the heat control circuit board MHCW
15 15
3
No modbus communi-
cation to pressure
transmitter
● Check modbus cable between heat control circuit board and
subsequent MPT
3005167-2022-02-02
Alarms
78/108