24
WT.050.455.000.DE.IM.0319
Functions
GMS
plus
4.
4.3
Alarms
The alarms are output via relay contacts and red LED.
Alarm settings
sensor channel I and II
Each sensor channel has one alarm 1 and alarm 2, which can
each be assigned different switching thresholds within the
measuring range.
You can set a delay time of 0 – 120 min for each alarm.
Each alarm can be defined as:
• N.O. contact (normal status = opened)
• N.C. contact (normal status = closed)
• unlatched
• latched with confirmation
See 4.3.1 “Alarm modes" on page 26.
Door contact input
A door contact input is integrated for each sensor channel.
For example, to switch off the sprinkler system when the gas room
doors are opened (see 4.5 “Door contact switch" on page 32).
When a door contact switch is used, local safety regulations must
be observed.
Sensor alarm
The sensor alarm is designed as a common alarm. The sensor
inputs can be freely assigned.
Multiple assignment is possible on:
• Sensor I
• Sensor II
• Temperature I
• Temperature II
If the defined sensor input signals are exceeded in either
direction(wire break, sensor error, etc.), the sensor alarm is
activated if this sensor is assigned to the sensor alarm.
You can select an ON delay of 0 – 5 min.
For Chloratect sensor, µA signal < 0.1 µA.
For mA-Sensor, mA signal < 4 mA.
Summary of Contents for WALLACE & TIERNAN GMS PLUS
Page 1: ...WALLACE TIERNAN GAS MONITORING SYSTEM GMS PLUS INSTRUCTION MANUAL...
Page 2: ...2 WT 050 455 000 DE IM 0319 GMS plus Please note Original instruction manual...
Page 20: ...20 WT 050 455 000 DE IM 0319 Description GMS plus 3...
Page 38: ...38 WT 050 455 000 DE IM 0319 Functions GMS plus 4...
Page 76: ...76 WT 050 455 000 DE IM 0319 Operation GMS plus 6 General overview...
Page 94: ...94 WT 050 455 000 DE IM 0319 Operation GMS plus 6...
Page 103: ...GMS plus Wiring diagrams 9 103 9 Wiring diagrams...
Page 104: ...104 WT 050 455 000 DE IM 0319 Wiring diagrams GMS plus 9...
Page 105: ...GMS plus Wiring diagrams 9 105...
Page 106: ...106 WT 050 455 000 DE IM 0319 Wiring diagrams GMS plus 9...
Page 107: ...GMS plus Wiring diagrams 9 107...
Page 108: ...108 WT 050 455 000 DE IM 0319 Wiring diagrams GMS plus 9...
Page 109: ...GMS plus Declaration of conformity 10 109 10 Declaration of conformity...
Page 110: ...110 WT 050 455 000 DE IM 0319 Declaration of conformity GMS plus 10...
Page 114: ...114 WT 050 455 000 DE IM 0319 Index GMS plus 11...