Display error message
Display
Meaning
Measures
"Sensor I ?"
Sensor I signal too
low or too high
Check electrolyte
supply
Check cable
connection to the
sensor.
Check sensor signal in
the Diagnosis menu.
"Sensor II?"
Sensor I signal too
low or too high
"Temp.I?"
Temperature sensor
I signal outside the
range
Check sensor/cable
connection, sensor
resistors:
0 °C => 1000 Ohm
10 °C => 1038.5 Ohm
20 °C => 1077 Ohm
50 °C => 1192.5 Ohm
"Temp.II?"
Temperature sensor
II signal outside the
range
"Range I ?"
Alarm values of
sensor I outside the
measurement range
Change the alarm
values in the menu.
"Range II ?"
Alarm value of
sensor II outside the
measurement range
"mA out ?"
Load on mA output
1, 2 or 3 greater than
600
Check mA connection
lines; may have a
open circuit or load is
too high
"Clock ?"
Real-time clock error
Send to us for repair
"battery ?"
Battery capacity too
low or battery
defective (i.e.
temperature
> 45 °C)
Change battery and
reduce ambient or
battery temperature
"Power fail ?“
Battery supply mains
voltage off
Switch power on
"Batt empty "
Mains voltage off
and battery empty
Switch power on
"EPROM ?"
Incompatible
software was
installed or the
system is defective.
Send to us for repair
Summary of Contents for WALLACE & TIERNAN GMS PLUS
Page 1: ...WALLACE TIERNAN GAS MONITORING SYSTEM GMS PLUS INSTRUCTION MANUAL...
Page 2: ...2 WT 050 455 000 DE IM 0319 GMS plus Please note Original instruction manual...
Page 20: ...20 WT 050 455 000 DE IM 0319 Description GMS plus 3...
Page 38: ...38 WT 050 455 000 DE IM 0319 Functions GMS plus 4...
Page 76: ...76 WT 050 455 000 DE IM 0319 Operation GMS plus 6 General overview...
Page 94: ...94 WT 050 455 000 DE IM 0319 Operation GMS plus 6...
Page 103: ...GMS plus Wiring diagrams 9 103 9 Wiring diagrams...
Page 104: ...104 WT 050 455 000 DE IM 0319 Wiring diagrams GMS plus 9...
Page 105: ...GMS plus Wiring diagrams 9 105...
Page 106: ...106 WT 050 455 000 DE IM 0319 Wiring diagrams GMS plus 9...
Page 107: ...GMS plus Wiring diagrams 9 107...
Page 108: ...108 WT 050 455 000 DE IM 0319 Wiring diagrams GMS plus 9...
Page 109: ...GMS plus Declaration of conformity 10 109 10 Declaration of conformity...
Page 110: ...110 WT 050 455 000 DE IM 0319 Declaration of conformity GMS plus 10...
Page 114: ...114 WT 050 455 000 DE IM 0319 Index GMS plus 11...