GMS
plus
Operation
6.
85
Display
Value range
(factory setting, bold)
Description
SENSOR I
Setting the parameters for the sensor to be
connected to sensor channel I
Sensor input I
Chloratect
mA signal
OFF (all menus for sensor channel I
are hidden and the associated
measured values are not displayed.)
Selection of sensors to be connected
Senso type I
For mA sensors:
Cl2
, ClO2, O3, SO3, HCL, ----
(variably definable type, max. 4
positions)
For Chloratect sensors (µA-Input):
Cl2
, ClO2 and O3
Setting the sensor type (i.e. the gas to be
measured)
Type def I
XXXX
Enter the sensor type for sensor I
for variable definition (A – Z, a – z, 0 – 9)
4 positions (freely selectable)
Sensor unit I
ppm
ml/m
3
---- (unit freely selectable, max. 4
positions for mA sensors)
Sensor I display unit
Unit def. I
XXXX
Entering the sensor unit for mA sensor I
for variable definition (A – Z, a – z, 0 – 9)
4 positions (freely selectable)
Range Start I
0 – 999 (mA sensor)
0.0
Measuring range start value for mA signal
sensor I
Measuring Range I/
Range End I
For mA sensors: 0 – 999
Display format 000.0 for value over
100
Display format 000 for values higher
than 100
or
For Chloratect sensors:
end value 1.5 or 20 ppm
O3 =>
1
ppm
Cl2 =>
5
ppm / 20 ppm
ClO2 =>
5
ppm / 20 ppm
Setting the measuring range for Chloratect
sensors and/or setting the measuring range
end value for mA sensors
Factor I
0.1 – 4.0 (for mA signal sensor)
1.0
Factor for adjusting the measuring range of
sensor I to range I of the GMS
plus
Temperature I
OFF
/ON
Temperature measurement I on/off
Summary of Contents for WALLACE & TIERNAN GMS PLUS
Page 1: ...WALLACE TIERNAN GAS MONITORING SYSTEM GMS PLUS INSTRUCTION MANUAL...
Page 2: ...2 WT 050 455 000 DE IM 0319 GMS plus Please note Original instruction manual...
Page 20: ...20 WT 050 455 000 DE IM 0319 Description GMS plus 3...
Page 38: ...38 WT 050 455 000 DE IM 0319 Functions GMS plus 4...
Page 76: ...76 WT 050 455 000 DE IM 0319 Operation GMS plus 6 General overview...
Page 94: ...94 WT 050 455 000 DE IM 0319 Operation GMS plus 6...
Page 103: ...GMS plus Wiring diagrams 9 103 9 Wiring diagrams...
Page 104: ...104 WT 050 455 000 DE IM 0319 Wiring diagrams GMS plus 9...
Page 105: ...GMS plus Wiring diagrams 9 105...
Page 106: ...106 WT 050 455 000 DE IM 0319 Wiring diagrams GMS plus 9...
Page 107: ...GMS plus Wiring diagrams 9 107...
Page 108: ...108 WT 050 455 000 DE IM 0319 Wiring diagrams GMS plus 9...
Page 109: ...GMS plus Declaration of conformity 10 109 10 Declaration of conformity...
Page 110: ...110 WT 050 455 000 DE IM 0319 Declaration of conformity GMS plus 10...
Page 114: ...114 WT 050 455 000 DE IM 0319 Index GMS plus 11...