92
WT.050.455.000.DE.IM.0319
Operation
GMS
plus
6.
Please note
The accuracy of the alarm function is not certain during the run-in
period.
Error diagnostics on
Chloratect sensors
Using a digital voltmeter, the DC voltages on the measuring cell
input can be measured (terminals 21 – 22 and 25 – 26). They are
used to trouble-shoot the sensors. The voltages are typical values
for appropriate zero balance currents:
• Cl
2
- and ClO
2
sensor at 1 µA:
approx. 1.1 – 1.3 V=
• O
3
-sensor at 0.3 µA:
approx. 0.35 – 0.45 V=
Please note
The sensor is defective or improperly enabled if the measured
voltage deviates from the specified values!
COMMON 1
COMMON 2
COMMON 3
red
flashing or
constant
Common alarm 1
active common relay 1
triggered
Follow alarm plan. For "latched"
mode: After removing the cause,
clear with the
key or external
acknowledge key. Remove
cause of alarm.
See 4.3 “Alarms" on page 24.
Common alarm 2
active common relay 2
triggered
Common alarm 3
active common relay 3
triggered
SENSOR
red
constant
Sensor current too low
or too high
Replenish the electrolyte in the
sensors.
Check the µA signal in the menu
Diagnosis.
Check the cable connection
between the sensors and the
GMS
plus
.
Sensor not yet run in; calibrate
after run-in period.
For
"latched"
mode: After
removing the cause, clear with
the
key or external
acknowledge key.
flashing
Sensor alarm latched
Sensor current too low
or too high
Display
Color
Meaning
Measures
Summary of Contents for WALLACE & TIERNAN GMS PLUS
Page 1: ...WALLACE TIERNAN GAS MONITORING SYSTEM GMS PLUS INSTRUCTION MANUAL...
Page 2: ...2 WT 050 455 000 DE IM 0319 GMS plus Please note Original instruction manual...
Page 20: ...20 WT 050 455 000 DE IM 0319 Description GMS plus 3...
Page 38: ...38 WT 050 455 000 DE IM 0319 Functions GMS plus 4...
Page 76: ...76 WT 050 455 000 DE IM 0319 Operation GMS plus 6 General overview...
Page 94: ...94 WT 050 455 000 DE IM 0319 Operation GMS plus 6...
Page 103: ...GMS plus Wiring diagrams 9 103 9 Wiring diagrams...
Page 104: ...104 WT 050 455 000 DE IM 0319 Wiring diagrams GMS plus 9...
Page 105: ...GMS plus Wiring diagrams 9 105...
Page 106: ...106 WT 050 455 000 DE IM 0319 Wiring diagrams GMS plus 9...
Page 107: ...GMS plus Wiring diagrams 9 107...
Page 108: ...108 WT 050 455 000 DE IM 0319 Wiring diagrams GMS plus 9...
Page 109: ...GMS plus Declaration of conformity 10 109 10 Declaration of conformity...
Page 110: ...110 WT 050 455 000 DE IM 0319 Declaration of conformity GMS plus 10...
Page 114: ...114 WT 050 455 000 DE IM 0319 Index GMS plus 11...