Operation
GMS
plus
6.
Please note
The temperature alarms can be linked via a common alarm using
a relay switch function.
Display
Value range
(factory setting, bold)
Description
TEMPERATURE
Includes the temperature alarm settings for
temperature sensor I and II
Alarmvalue Min l
0 – 50 (°C)
15 °C
Min. alarm value for temperature sensor I
Alarmvalue Max I
0 – 50 (°C)
35 °C
Max. alarm value for temperature sensor I
Alarmdelay l
0...30 min
10min
Alarm delay for min or max temperature
alarm for temperature sensor I
Alarmvalue Min lI
0 – 50 (°C)
15 °C
Min. alarm value for temperature sensor II
Alarmvalue Max lI
0 – 50 (°C)
15 °C
Max. alarm value for temperature sensor II
Alarmdelay lI
0 – 30 min
10min
Alarm delay for min or max alarm for
temperature sensor II
Summary of Contents for WALLACE & TIERNAN GMS PLUS
Page 1: ...WALLACE TIERNAN GAS MONITORING SYSTEM GMS PLUS INSTRUCTION MANUAL...
Page 2: ...2 WT 050 455 000 DE IM 0319 GMS plus Please note Original instruction manual...
Page 20: ...20 WT 050 455 000 DE IM 0319 Description GMS plus 3...
Page 38: ...38 WT 050 455 000 DE IM 0319 Functions GMS plus 4...
Page 76: ...76 WT 050 455 000 DE IM 0319 Operation GMS plus 6 General overview...
Page 94: ...94 WT 050 455 000 DE IM 0319 Operation GMS plus 6...
Page 103: ...GMS plus Wiring diagrams 9 103 9 Wiring diagrams...
Page 104: ...104 WT 050 455 000 DE IM 0319 Wiring diagrams GMS plus 9...
Page 105: ...GMS plus Wiring diagrams 9 105...
Page 106: ...106 WT 050 455 000 DE IM 0319 Wiring diagrams GMS plus 9...
Page 107: ...GMS plus Wiring diagrams 9 107...
Page 108: ...108 WT 050 455 000 DE IM 0319 Wiring diagrams GMS plus 9...
Page 109: ...GMS plus Declaration of conformity 10 109 10 Declaration of conformity...
Page 110: ...110 WT 050 455 000 DE IM 0319 Declaration of conformity GMS plus 10...
Page 114: ...114 WT 050 455 000 DE IM 0319 Index GMS plus 11...