86
WT.050.455.000.DE.IM.0319
Operation
GMS
plus
6.
Display
Value range
(factory setting, bold)
Description
SENSOR II
Setting the parameters for the sensor to be
connected to sensor channel II
Sensor input II
Chloratect
mA signal
OFF (all menus for sensor channel I
are hidden and the associated
measured values are not displayed.)
Selection of sensors to be connected
Sensortype II
For mA sensors:
Cl2
, ClO2, O3, SO3, HCL, ----
(variably definable type, max. 4
positions)
For Chloratect sensors (µA-Input):
Cl2
, ClO2 and O3
Setting the sensor type (i.e. the gas to be
measured)
Type def II
XXXX
Enter the sensor type for sensor II
for variable definition (A – Z, a – z, 0 – 9)
4 positions (freely selectable)
Sensor unit II
ppm
ml/m
3
---- (unit freely selectable, max. 4
positions for mA sensors)
Sensor II display unit
Unit def. II
XXXX
Entering the sensor unit for mA sensor II
for variable definition (A – Z, a – z, 0 – 9)
4 positions (freely selectable)
Range Start II
0 – 999 (mA sensor)
0.0
Measuring range start value for mA signal
sensor II
Measuring Range II/
Range End II
For mA sensors: 0...999
Display format 000.0 for value over
100
Display format 000 for values higher
than 100
or
For Chloratect sensors:
end value 1.5 or 20 ppm
O3 =>
1
ppm
Cl2 =>
5
ppm / 20 ppm
ClO2 =>
5
ppm / 20 ppm
Setting the measuring range for Chloratect
sensors and/or setting the measuring range
end value for mA sensors
Factor II
0.1 – 4.0 (for mA signal sensor)
1.0
Factor for adjusting the measuring range of
sensor II to range II of the GMS
plus
Temperature II
OFF
/ON
Temperature measurement II on/off
Summary of Contents for WALLACE & TIERNAN GMS PLUS
Page 1: ...WALLACE TIERNAN GAS MONITORING SYSTEM GMS PLUS INSTRUCTION MANUAL...
Page 2: ...2 WT 050 455 000 DE IM 0319 GMS plus Please note Original instruction manual...
Page 20: ...20 WT 050 455 000 DE IM 0319 Description GMS plus 3...
Page 38: ...38 WT 050 455 000 DE IM 0319 Functions GMS plus 4...
Page 76: ...76 WT 050 455 000 DE IM 0319 Operation GMS plus 6 General overview...
Page 94: ...94 WT 050 455 000 DE IM 0319 Operation GMS plus 6...
Page 103: ...GMS plus Wiring diagrams 9 103 9 Wiring diagrams...
Page 104: ...104 WT 050 455 000 DE IM 0319 Wiring diagrams GMS plus 9...
Page 105: ...GMS plus Wiring diagrams 9 105...
Page 106: ...106 WT 050 455 000 DE IM 0319 Wiring diagrams GMS plus 9...
Page 107: ...GMS plus Wiring diagrams 9 107...
Page 108: ...108 WT 050 455 000 DE IM 0319 Wiring diagrams GMS plus 9...
Page 109: ...GMS plus Declaration of conformity 10 109 10 Declaration of conformity...
Page 110: ...110 WT 050 455 000 DE IM 0319 Declaration of conformity GMS plus 10...
Page 114: ...114 WT 050 455 000 DE IM 0319 Index GMS plus 11...