4.10
Battery supply (optional)
The GMS
plus
comes optionally with a 24 V battery supply. This is
only available together with a 24 V gas monitoring system
GMS
plus
.
The battery supply is connected to the GMS
plus
with a pre-wired
plug connector.
An 8-pin socket is installed on the GMS
plus
. A 1.5 m long
connection cable with 8-pin plug is attached to the battery module.
This connection cable is plugged into the GMS
plus
.
Please note
A protective ground connection must be made separately on the
GMS
plus
.
The battery supply switches from the mains to the battery without
interruption.
Please note
A charged battery will bridge a power failure of at least 10 hours.
The operating duration is less with additionally connected
consumer units!
The GMS
plus
is fully operational during this time.
The batteries are charged automatically and by temperature
during mains operation.
Battery supply voltage
During commissioning the GMS
plus
is not supplied with 24 V
from the battery supply before power has been applied to the
battery supply.
Please note
The connecting plug to the battery module must be removed in
advance of repair on or replacement of the GMS PCB to ensure it
does not carry any voltage.
Summary of Contents for WALLACE & TIERNAN GMS PLUS
Page 1: ...WALLACE TIERNAN GAS MONITORING SYSTEM GMS PLUS INSTRUCTION MANUAL...
Page 2: ...2 WT 050 455 000 DE IM 0319 GMS plus Please note Original instruction manual...
Page 20: ...20 WT 050 455 000 DE IM 0319 Description GMS plus 3...
Page 38: ...38 WT 050 455 000 DE IM 0319 Functions GMS plus 4...
Page 76: ...76 WT 050 455 000 DE IM 0319 Operation GMS plus 6 General overview...
Page 94: ...94 WT 050 455 000 DE IM 0319 Operation GMS plus 6...
Page 103: ...GMS plus Wiring diagrams 9 103 9 Wiring diagrams...
Page 104: ...104 WT 050 455 000 DE IM 0319 Wiring diagrams GMS plus 9...
Page 105: ...GMS plus Wiring diagrams 9 105...
Page 106: ...106 WT 050 455 000 DE IM 0319 Wiring diagrams GMS plus 9...
Page 107: ...GMS plus Wiring diagrams 9 107...
Page 108: ...108 WT 050 455 000 DE IM 0319 Wiring diagrams GMS plus 9...
Page 109: ...GMS plus Declaration of conformity 10 109 10 Declaration of conformity...
Page 110: ...110 WT 050 455 000 DE IM 0319 Declaration of conformity GMS plus 10...
Page 114: ...114 WT 050 455 000 DE IM 0319 Index GMS plus 11...