Section 40
00-02-0787
2015-03-23
~ 29 ~
S-#
Description
S49
HI DISCH PSI: (S45 is only visible if S35 = Transducer & S37 =
Pressure.) When “pressure” is selected in either the start / stop or
throttle type, an immediate shutdown will occur if the pressure rises to
this set point. (adjustable from 0 to 1000 PSI)
Factory set to 90.
Entering “0” disables this function. When enabled, pressure is
displayed on the front display regardless what is entered in S35 and
S36.
S50
LOW DISCH PSI: (S45 is only visible if S35 = Transducer & S37 =
Pressure.) When “pressure” is selected in either the start / stop or
throttle type, an immediate shutdown will occur if the pressure drops
to this set point (adjustable from 0 to 1000 PSI)
Factory set to 25.
Entering “0” disables this function. When enabled, pressure is
displayed on the front display regardless what is entered in S35 and
S36.
S51
AT LOAD DLY: (S45 is only visible if S35 = Transducer & S37 =
Pressure.) This delay begins timing after the warm-up delay expires.
The Low Discharge Pressure shutdown is armed when this delay
expires (adjustable from 1 to 9,999 seconds).
Factory set to 180.
S52
FILL MODE DLY: (S45 is only visible if S35 = Transducer & S37 =
Pressure.) This delay begins timing after the warm-up delay expires.
The engine is held at the minimum RPM set point until this delay
expires (adjustable from 1 to 9,999 seconds).
Factory set to 0.
S53
PRESSURE MAX: (S45 is only visible if S35 = Transducer & S37 =
Pressure.) Set this to the maximum value of the pressure transducer.
For example, if the transducer range is 0-100 PSI, enter 100.
(adjustable from 0 to 5000 PSI)
Factory set to 100 PSI.
S54
PRESSURE MIN: (S45 is only visible if S35 = Transducer & S37 =
Pressure.) Set this to the minimum value of the pressure transducer.
For example, if the transducer range is 0-100 PSI, enter 0.
Factory
set to 0.
S55
PSI XDUCER MAX CNT: (S45 is only visible if S35 = Transducer &
S37 = Pressure.) With 5 VDC or 20mA applied to the analog channel,
make the top line read the same value as the bottom line.
Factory set to 904.
(This is the setting for 4-20mA signal) If the
transducer is 0-5 VDC, enter 1023 in this set point.
Summary of Contents for Murphy EMS PRO LITE
Page 4: ......
Page 8: ...NOTES ...
Page 22: ...Section 40 00 02 0787 2015 03 23 14 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 60: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 61: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 62: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 63: ......