Section 40
00-02-0787
2015-03-23
~ 36 ~
M3
Hex View
For reading ram locations from 0000H to FFFFH.
Factory set to 00H
.
M4
Force Output
Using the down arrow to move the cursor under
the correct output. From left to right, outputs are
1-7. Turn on the output using the up arrow button,
and off by using the down arrow.
M5
Force LED
This allows the user to force the LEDs ON when
they are not active. This action is to ensure the
LEDs are working.
M6
An Out 1 Duty
The VDC on the analog out channel can be
increased and decreased by changing the duty
value.
Factory set to 0.
M7
Factory Setups
Select YES to force factory settings into all of the
applicable S, P, and M numbers. After pressing
YES, the display will go from NO to YES. Allow
the controller to return to NO before exiting the M
number.
M8
SCADA ALARM
Selecting yes will enable the SCADA comm.
alarm.
Factory set to NO.
M9
SCADA AL DLY
This delay is only used if the SCADA alarm
enable (M8) is set to YES. There is only one set
point for both ports (232 and 485), but they each
have their own timers. The delay starts timing on
power up of the unit. The delay is restarted
anytime a MODBUS packet is received on the
associated port. If the delay times-out an alarm
only message is displayed:
SCADA FAILURE
.
This warning message ends as soon as MODBUS
packets resume on the port.
M10
SYS V MAX
This number calibrates the controller to the
incoming battery voltage. Improper readings may
occur on sender inputs if this set point is not 30.5.
Factory set to 30.5.
M11
Run HRS RST
This is the 1000 portion of the engine running
hourmeter. This set point can be used reset the
hourmeter to zero, or enter the correct running
hours in 1000’s.
Factory set to 0.
M12
Tenth HR RST
This is the 100.0 portion of the engine running
hourmeter. This set point can be used reset the
hourmeter to zero, or enter the correct running
hours in 100.0’s.
Factory set to 0.
M13
Oil P Lockout
This is a bubble timer to ignore fluctuations in the
oil pressure reading and prevent false shutdowns.
(adjustable from 1 to 4 seconds)
Factory set to 1.
M14
Can 0 Address
This is the source address for can port 0.
Factory
set to 3.
Summary of Contents for Murphy EMS PRO LITE
Page 4: ......
Page 8: ...NOTES ...
Page 22: ...Section 40 00 02 0787 2015 03 23 14 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 60: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 61: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 62: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 63: ......