![Enovation Controls Murphy EMS PRO LITE Installation And Operation Manual Download Page 54](http://html.mh-extra.com/html/enovation-controls/murphy-ems-pro-lite/murphy-ems-pro-lite_installation-and-operation-manual_2413866054.webp)
Section 40
00-02-0787
2015-03-23
~ 46 ~
REGISTER
#
TYPE
DESCRIPTION
40008
Read Only
Shutdown Status: Bits description follows:
Bit 0
(LSB) Low Oil Pressure: (1) yes, (0) no.
Bit 1
High Engine Temperature: (1) yes, (0)
no.
Bit 2
Spare
Bit 3
Spare
Bit 4
Loss of Speed: (1) yes, (0) no.
Bit 5
No Speed Signal: (1) yes, (0) no.
Bit 6
Overspeed: (1) yes, (0) no.
Bit 7
Overcrank: (1) yes, (0) no.
Bit 8
High Discharge Pressure: (1) yes, (0)
no.
Bit 9
Low Discharge Pressure: (1) yes, (0)
no.
Bit 10 High System Level: (1) yes, (0) no.
Bit 11 Low System Level: (1) yes, (0) no.
Bit 12
Loss of Pressure Sender: (1) yes, (0)
no.
Bit 13 Spare
Bit 14 Spare
Bit 15 Spare
40009
Read Only
Shutdown Status: Bits description follows:
Bit 0
Reserved
Bit 1
Low Fuel Level Alarm: (1) yes, (0) no.
Bit 2
Low Fuel Level Shutdown: (1) yes, (0)
no.
Bit 3
Spare.
Bit 4
Spare.
Bit 5
Spare.