Section 40
00-02-0787
2015-03-23
~ 40 ~
Digital
Output
Description
Connector
1
Fuel/Ignition/ECU Enable (B+)
Pin G, 21 Pos. Conn. from
R1 relay
2
Reserved
3
Alt Excite (B+)
4
Throttle Decrease (Murphy Throttle
Actuator AT-03069)
Pin R, 21 Pos. Conn
5
Throttle Increase ((Murphy Throttle
Actuator AT-03069)
Pin S 21 Pos. Conn
6
Reserved
7
Reserved
8
Prestart (B-)
Pin E, 9 Pos Conn
9
Reserved
10
Crank (B+)
Pin D, 21 Pos. Conn. from
R2 relay
11
Reserved
12
Reserved
PCBA Shunts
Reference this section for default positions of the Shunt Jumpers on the
PCBA’s.
RS485 Terminating Resistor (LK3 Shunt):
This shunt allows a terminating resistor to be used on the RS485 port.
(Default ON)
•
ON – (Jumper Installed) allows the terminating resistor to be
present.
•
OFF – (Jumper Removed) removes terminating resistor from the
RS485.
Sender Shunt (LK5 Shunt):
This shunt controls sender power (Default ON). This shunt must be
installed to use senders. It can be removed when no senders are being
used to reduce heat buildup inside the controller. This is only of interest
in systems with battery voltage of 12VDC.
•
ON – (Jumper Installed) allows sender resistor power for
Mechanical engines using senders.
•
OFF – (Jumper Removed) When the program is not using
senders, this shunt can be removed.
Summary of Contents for Murphy EMS PRO LITE
Page 4: ......
Page 8: ...NOTES ...
Page 22: ...Section 40 00 02 0787 2015 03 23 14 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 60: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 61: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 62: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 63: ......