Section 40
00-02-0787
2015-03-23
~ 16 ~
The start condition must remain active throughout the start
delay, or the delay will reset to zero.
•
When the “START DELAY” expires, the following will occur:
The STATE: text line will display “PRESTART DELAY”.
The “prestart delay” begins timing.
The prestart output turns ON.
•
When the “PRESTART DELAY” expires, the following will occur:
The STATE: text line will display “CRANK ON/OFF”.
The following shutdown circuits are armed:
-
Low Coolant Level
-
High/Low Oil Level
-
High Discharge Pressure
-
Overspeed
-
Overcrank
-
Low Fuel Level (Self-clearing alarm only)
-
XDUCER OOR (Out of Range) HIGH (Only if float
backup not selected)
-
XDUCER OOR (Out of Range) LOW (Only if float
backup not selected)
-
High System Level (Self-clearing alarm or shutdown)
-
LO System Level (Self-clearing alarm or shutdown)
•
The fuel/ECU enable output is turned ON.
NOTE
the following:
WAIT FOR ECU
: If ECU is selected in engine type, the
controller will go through a fixed 10-second delay to allow the
ECU to warm up prior to cranking.
A
NO SPEED SIGNAL
shutdown will occur (when enabled) if
the controller does not read a frequency within 3 seconds after
cranking begins.
The Alt excite output is turned ON.
The crank output is turned ON and cycle cranking begins at
this point for all engine types.
NOTE
:
CYCLE CRANKING
If the engine does not start on the first crank, the controller will
de-energize the starter output for the rest cycle.
Summary of Contents for Murphy EMS PRO LITE
Page 4: ......
Page 8: ...NOTES ...
Page 22: ...Section 40 00 02 0787 2015 03 23 14 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 60: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 61: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 62: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 63: ......