49
CTC EcoLogic Pro/Family
For the property owner
!
The setpoint of the cooling fl ow is
linear b20
°C
and +40
°C.
Cooling
Cooling permit. from outdoor T °C
Off
Flow temp. at outdoor temp. +20°C 20
Flow temp. at outdoor temp. +40°C 10
Min. fl ow temp. °C
18
Start cooling at overtemp.
1.0
Stop cooling at overtemp.
0.5
Smart low price. ºC
1
Smart over capcity. ºC
2
4.5.2.10 Communication
Settings to control the product with a controlling
system. The CTC BMS accessory is needed to use this
function. See the CTC BMS accessory manual for more
information.
4.5.2.11 Save settings
Here you can save your own settings. Coni rm using the
“OK” button.
4.5.2.12 Load settings
The saved settings can be reloaded.
4.5.2.13 Load factory settings
The product is supplied with the factory values set. They
can be restored by activating this function. Press OK to
coni rm. However, the language, product and product
size are retained.
Communication
MB address
1
Baud rate
9600
Parity Even
Stop bit
1
4.5.2.9 Cooling*
Cooling permit. from outdoorT °C From (0 to 39/
From)
The outdoor temperature from which cooling will be
permitted is determined in this menu. At outdoor
temperatures lower than the set value, cooling is not
“On”.
Primary l ow at outdoor temp +20°C
20 (2 to 20)
The temperature of the cooling l ow at an outdoor
temperature of 20°C is determined in this menu.
Primary l ow at outdoor temp +40°C
10 (2 to 20)
The temperature of the cooling l ow at an outdoor
temperature of 40°C is determined in this menu.
Min. primary l ow °C
18 (2 to 25)
The minimum setpoint of the cooling l ow is determined
in this menu.
The l ow temperature is displayed in the
Operation data
EcoLogic/Heating circuit 2–4 menu.
Start cooling at overtemp.
1.0 (0.5 to 15.0)
The overtemperature in the room at which cooling will
start is determined in this menu.
Stop cooling at overtemp.
0.5 (0.1 to 14.0)
The overtemperature in the room at which cooling will
stop is determined in this menu.
Smart low price ºC
1 (Off, 1...5 )
Find out more in “Dei ne/Remote control/Smart Grid”.
Smart overcap. ºC
1 (Off, 1...5 )
Find out more in “Dei ne/Remote control/Smart Grid”.
See CTC EcoComfort manual for more
information.
*Applies to the CTC EcoLogic PRO only.
Summary of Contents for CTC EcoLogic Family series
Page 2: ......
Page 3: ...162 105 48 3 2016 04 08 Installation and Maintenance Manual CTC EcoLogic Pro Family...
Page 67: ...67 CTC EcoLogic Pro Family For the property owner...
Page 120: ...120 CTC EcoLogic Pro Family For the installer 11 Wiring diagram...
Page 121: ...121 CTC EcoLogic Pro Family For the installer...
Page 127: ......