CTC EcoLogic Pro/Family
For the property owner
4.5.2.3 Additional heat
Start add E1, degree min
-500 (-900 to -30)
This menu is used to dei ne at how many degree
minutes additional heat E1 should start to operate.
Applies to EcoLogic systems 1, 2 and 3 only.
Diff add E1, degree min
-100 (-300 to -20)
This menu is used to dei ne the difference in degree
minutes between the start and stop conditions for
additional heat E1. If additional heat is set to start at
-500 degree minutes, it will be stopped at -400 degree
minutes (based on a difference setting of
-100).
Applies to EcoLogic systems 1, 2 and 3 only.
Start 0–10 V E2, degree min*
-500 (-900 to -30)
This menu is used to dei ne at how many degree
minutes the electric boiler (E2) should start to operate.
Applies to EcoLogic systems 2 and 3 only.
Diff 0-10V E2, degree min*
-100 (-300 to -20)
This menu is used to dei ne the difference in degree
minutes between the start and stop conditions for the
electric boiler. If the electric boiler is started at -500
degree minutes, it will be stopped at -400 degree
minutes (based on a difference setting of
-100).
Applies to EcoLogic systems 2 and 3 only.
EcoMiniEl (E3)
No(No/1/2/3)
Set to indicate whether or not EcoMiniEl (E3) is
connected. Also specify whether the immersion heater
is to connect 1, 2 or 3 steps. Valid for EcoLogic
systems 2, 3 and 4.
Start EcoMiniEl, degree min
-500 (-900 to -30)
This menu is used to dei ne at how many degree
minutes EcoMiniEl (E3) will start.
Applies to EcoLogic systems 1, 2 and 3 only.
Diff steps EcoMini
-50 (-300 to -20)
This menu is used to dei ne the difference in degree
minutes between the start and stop conditions for
EcoMiniEl. If the electric boiler is started at -500 degree
minutes, it will be stopped at -450 degree minutes
(based on a difference setting of
-50).
Applies to EcoLogic systems 1, 2 and 3 only.
Delay add E1
180 (30 to 480)
This menu is used to state when additional heat E1 is
started. The delay in minutes of subnormal temperature
in the buffer tank required before additional heat E1 is
started.
Applies to EcoLogic systems 4, 5 and 6 only.
Diff add E1 delay.
60 (10 to 120)
This function is not activated for this product.
*Applies to the CTC EcoLogic PRO only.
System
Family
1
2
3
Pro
System
Family
4
5
6
Pro
System
2
3
Pro
System
Family
2
3
4
Pro
System
Family
2
3
Pro
System
Family
4
Pro
Additional heat
Start E1, degree minute
-500
Diff. E1, degree minute
-100
Start 0-10V, ºminute
-500
Diff. 0-10V , ºminute
-100
Start EcoMiniEl, ºminute
-500
Diff. step EcoMiniEl
-50
Delay add heat E1
180
Delay add heat 0-10V E2
180
Diff. 0-10V E2 delay
60
Summary of Contents for CTC EcoLogic Family series
Page 2: ......
Page 3: ...162 105 48 3 2016 04 08 Installation and Maintenance Manual CTC EcoLogic Pro Family...
Page 67: ...67 CTC EcoLogic Pro Family For the property owner...
Page 120: ...120 CTC EcoLogic Pro Family For the installer 11 Wiring diagram...
Page 121: ...121 CTC EcoLogic Pro Family For the installer...
Page 127: ......