3. Technical data
Supply
230 V 1N~
Max. fuse size
10 A
Total max. load CTC EcoLogic
10 A
Max. load relay output
4 A
Electrical data diverting valve
230 V 1N~
Electrical mixing valve motor
230 V 1N~
Output additional heat
(external additional heat source E1, E4)
230 V 1N~, max. 4 A
Sensor (protective extra low voltage),
NTC 22k, °C/ohm
0/66k, 10/41.8k, 15/33.5k, 20/27.1k, 25/22k, 30/18k,
35/14.8k, 40/12.2k, 50/8.4k, 60/6.0k, 70/4.3k,
80/3.1k, 90/2.3k, 100/1.7k
Hot gas sensor, NTC 3.3 type,
°C/ohm
20/61.5k, 30/39.5k, 40/26k, 50/17.5k,
60/12.1k, 70/8.5k, 80/6.1k, 90/4.5k, 100/3.3k,
110/2.5k,120/1.9k, 130/1.5k, 150/0.9k
Outdoor sensor, NTC 150 type,
°C/ohm
-20/1.11k, -10/681, 0/428, 10/276, 20/182, 30/123,
40/85
Solar panel sensors*, PT1000 type,
°C/ohm
-10/960, 0/1000, 10/1039, 20/1077, 30/1116,
40/1155, 50/1194, 60/1232, 70/1271, 80/1309,
90/1347, 100/1385, 120/1461, 140/1535
Display
Memory
Back-up batteries
Clock
4.3 inches, colour, touch
maintains the memory in the event of a power failure
not needed
real-time
Measurements (w x h x d)
-display
-electrical connection box
159 x 160 x 28.1 mm
479 x 283 x 121 mm
*Applies to the CTC EcoLogic PRO
only.
Summary of Contents for CTC EcoLogic Family series
Page 2: ......
Page 3: ...162 105 48 3 2016 04 08 Installation and Maintenance Manual CTC EcoLogic Pro Family...
Page 67: ...67 CTC EcoLogic Pro Family For the property owner...
Page 120: ...120 CTC EcoLogic Pro Family For the installer 11 Wiring diagram...
Page 121: ...121 CTC EcoLogic Pro Family For the installer...
Page 127: ......