Prosonic S FMU95

PROFIBUS DP

Ultrasonic measuring technology

Level measurement

5 or 10 sensors

BA00344F/00/EN/16.21

71526736

2021-05-31

Summary of Contents for Prosonic S FMU95 PROFIBUS DP

Page 1: ...Products Solutions Services Operating Instructions Prosonic S FMU95 PROFIBUS DP Ultrasonic measuring technology Level measurement 5 or 10 sensors BA00344F 00 EN 16 21 71526736 2021 05 31 ...

Page 2: ...Prosonic S FMU95 PROFIBUS DP 2 Endress Hauser Order code Ext ord cd Ser no www endress com deviceviewer Endress Hauser Operations App XXXXXXXXXXXX XXXXX XXXXXX XXX XXXX XX Serial number 1 3 2 A0023555 ...

Page 3: ...ectrical connection 21 6 1 Connection conditions 21 6 2 Connecting the device 21 6 3 Special connection instructions 25 7 Operating options 38 7 1 Structure and function of the operating menu 38 7 2 Access to the operating menu via the local display 39 8 System integration 43 8 1 Overview of device description files 43 8 2 Additional settings 43 9 Commissioning 46 9 1 Preparatory steps 46 9 2 Swit...

Page 4: ...on will result in serious or fatal injury WARNING This symbol alerts you to a dangerous situation Failure to avoid this situation can result in serious or fatal injury CAUTION This symbol alerts you to a dangerous situation Failure to avoid this situation can result in minor or medium injury NOTICE This symbol contains information on procedures and other facts which do not result in personal injur...

Page 5: ...itted Procedures processes or actions that are permitted Preferred Procedures processes or actions that are preferred Forbidden Procedures processes or actions that are forbidden Tip Indicates additional information Reference to documentation Reference to graphic Notice or individual step to be observed 1 2 3 Series of steps Result of a step Visual inspection Operation via operating tool Write pro...

Page 6: ... TI Planning aid The document contains all the technical data on the device and provides an overview of the accessories and other products that can be ordered for the device 1 3 2 Brief Operating Instructions KA Guide that takes you quickly to the 1st measured value The Brief Operating Instructions contain all the essential information from incoming acceptance to initial commissioning 1 3 3 Safety...

Page 7: ...lusively by trained specialists authorized to perform such work by the system operator Technical personnel must have read and understood these Operating Instructions and must adhere to them Modifications and repairs to the device may only be carried out if they are expressly permitted in the Operating Instructions 2 3 Operational safety and process safety Alternative monitoring measures must be ta...

Page 8: ...plate 5 Cover of terminal compartment 6 Display and operating module 7 Precut openings for cable entries 8 Grounding terminal block 9 Display cable 10 Brief Operating Instructions 3 2 Product layout aluminum field housing Valid for Order code 030 housing material Option 3 aluminum field mounting IP66 NEMA4x Mad D 79 6 Pro Ta Xaxx Dat X 1 Ord e Ser 5 2 3 4 1 A0033256 2 Parts of the Prosonic S in th...

Page 9: ...Cover of terminal compartment 3 Nameplate 4 Device designation and identification 5 Brief Operating Instructions 6 Display cable 7 Terminals One possible version of the DIN rail housing is illustrated in the graphic above The housing may be narrower or wider depending on the device version 3 4 Product layout remote display and operating module for cabinet door and panel mounting Valid for Order co...

Page 10: ...ay and operating module 1 DIN rail housing without display and operating module 2 Remote display and operating module for mounting in a cabinet 3 The cable 3m 9 8 ft is supplied One possible version of the DIN rail housing is illustrated in the graphic above The housing may be narrower or wider depending on the device version ...

Page 11: ...e available for the identification of the measuring device Nameplate specifications Order code with breakdown of the device features on the delivery note Enter the serial number on the nameplate into W M Device Viewer www endress com deviceviewer all the information about the measuring device is displayed Enter the serial number on the nameplate into the Endress Hauser Operations App or scan the 2...

Page 12: ...nic S FMU95 PROFIBUS DP 12 Endress Hauser 4 3 Storage transport Pack the device so that it is protected against impact for storage and transportation The original packaging provides optimum protection Permitted storage temperature 40 to 60 C 40 to 140 F ...

Page 13: ...bonate field housing Unit of measurement mm in A Housing bracket supplied can also be used as a drilling template B Polycarbonate field housing C Minimum mounting clearance Mount the housing bracket on a level surface so that it cannot become warped or bent Otherwise it may be difficult or impossible to mount the polycarbonate field housing Mounting location Shaded location protected from direct s...

Page 14: ... also be used as a drilling template Mount the housing bracket on a level surface so that it cannot become warped or bent 1 1 2 3 4 A0032558 7 Wall mounted polycarbonate field housing 1 Housing bracket supplied Post mounting 1 A0034923 8 Mounting plate for mounting the polycarbonate field housing on a post 1 Housing bracket supplied ...

Page 15: ...m field housing 180 7 09 180 7 09 202 7 95 181 7 13 232 9 13 55 2 17 55 2 17 7 0 28 11 0 43 A0033258 9 Dimensions of Prosonic S with aluminum field housing Unit of measurement mm in Mounting location Shaded location protected from direct sunlight If mounting outdoors use a surge arrester Altitude install at a maximum altitude of 2000 m 6560 ft over MSL Minimum clearance to the left 55 mm 2 17 in t...

Page 16: ...Installation Prosonic S FMU95 PROFIBUS DP 16 Endress Hauser 5 2 2 Mounting the device Mad D 7 96 Pr o Ta Xax x Dat X 1 Ord e Ser A0033331 10 Wall mounted aluminum field housing ...

Page 17: ...TH 35x7 5 15 1 4x0 3 0 6 35 1 38 43 1 69 A0034908 11 Dimensions of Prosonic S with DIN rail housing Unit of measurement mm in Mounting location In cabinet outside hazardous areas At a sufficient distance from high voltage electric cables motor cables contactors or frequency converters Altitude install at a maximum altitude of 2000 m 6560 ft over MSL Minimum clearance to the left 10 mm 0 4 in the h...

Page 18: ... measurement mm in Mounting in remote display of Prosonic FMU860 861 862 This mounting method is suitable if FMU9x replaces the FMU86x predecessor model both with a remote display module Order number for adapter plate 52027441 1 2 A0032562 14 Mounting in remote display of FMU860 861 862 1 Remote display of Prosonic S with adapter plate 2 Opening of remote display of the FMU860 861 862 5 4 2 Mounti...

Page 19: ... FDU80 80F 81 81F 82 83 84 85 86 96 can no longer be ordered The Prosonic S transmitter can still be connected if the sensors are already installed 5 6 Post installation check Perform the following checks after mounting the device Is the device undamaged visual inspection Does the device match the measuring point specifications such as process temperature process pressure ambient temperature measu...

Page 20: ...ress Hauser Is the device firmly seated on the DIN rail is the device correctly mounted on the field housing bracket visual inspection Are the cover screws on the connection compartment cover of the field housing tightened securely visual inspection ...

Page 21: ...tion 0 25 to 2 5 mm2 24 to 14 AWG Min stripping length 10 mm 0 39 in 6 2 Connecting the device 6 2 1 Terminal compartment of polycarbonate field housing Valid for Order code 030 housing material Option 1 PC field mounting IP66 NEMA4x Access to terminal compartment 1 2 3 A0034895 16 Access to terminal compartment in polycarbonate field housing 1 2 3 A0034896 17 For easier wiring remove the cover fr...

Page 22: ...ial PML To route the cables only use cable glands that meet the explosion protection requirements at the place of operation Access to terminal compartment Mad D 79 6 Pro Ta Xaxx Dat X 1 Ord e Ser 5 2 3 4 1 A0033256 18 Access to terminal compartment in aluminum field housing 1 Aluminum field housing open 2 Nameplate 3 Terminal for protective ground 4 Display and operating module 5 Aluminum field ho...

Page 23: ...l connection Endress Hauser 23 Access to terminal compartment 1 2 3 A0038771 19 Access to terminal compartment single DIN rail housing unit 1 2 3 A0038772 20 Access to terminal compartment several DIN rail housing units mounted side by side ...

Page 24: ...D FDU Sensor A0035251 21 Terminal areas of Prosonic S FMU95 Terminals for power supply AC version Terminal 1 L 90 to 253 VAC Terminal 2 N Terminal 3 potential equalization Fuse 400 mA T Terminals for power supply DC version Terminal 1 L 10 5 to 32 VDC Terminal 2 L Terminal 3 potential equalization Fuse 2AT Terminals for level inputs In all device versions Sensor 1 terminals 9 yellow 10 black 11 re...

Page 25: ...rm Bus termination Address Device bus address 6 3 Special connection instructions 6 3 1 Connecting the power supply LCAUTION To guarantee electrical safety Fix the power supply cables securely in place when installing so they are permanently connected to the electrical installations for the building When connecting to the public mains install a mains switch for the device such that it is within ea...

Page 26: ...he polycarbonate field housing 1 Terminal block in field housing for potential equalization 2 Potential equalization wired on delivery Connection of the power supply in the aluminum field housing Valid for Order code 030 housing material Option 3 aluminum field mounting IP66 NEMA4x LWARNING Shock Hazard and Explosion Hazard Connect the aluminum field housing to the potential earth PE and or the lo...

Page 27: ... PE 4 A0035933 23 Connection of the power supply in the aluminum field housing 1 Potential equalization in aluminum field housing wired on delivery 2 Protective ground terminal strip with contact to DIN rail 3 Protective ground terminal on outside of field housing 4 Power supply Connection of the power supply in the DIN rail housing Valid for Order code 030 housing material Option 2 DIN rail mount...

Page 28: ... Operating Instructions BA00034S PROFIBUS DP PA Guidelines for planning and commissioning Cable specification For transmission rates up to 12 Mbit s use cable type A according to EN 50170 Characteristic impedance 135 to 165 Ω at a measuring frequency of 3 to 20 MHz Cable capacitance 30 pF m Wire cross section 0 34 mm2 22 AWG Wires twisted pairs 1x2 2x2 or 1x4 conductors Loop resistance 110 Ω km Si...

Page 29: ... connect the black wire shield to the BK terminal For extension cables twist the shield and connect to the BK terminal LWARNING Explosion Hazard Do not connect FDU83 FDU84 FDU85 and FDU86 sensors with an ATEX FM or CSA certificate to the FMU90 or FMU95 transmitters For the sensors FDU91F 93 95 96 and FDU83 84 85 86 connect the ground cable GNYE to local potential equalization after a maximum dista...

Page 30: ... m FDU91F 93 95 GNYE 1 2 3 A FDU91F 93 95 1 B FDU91F 93 95 YE BK RD YE BK RD FMU95 FMU95 BK YE RD BK YE RD GNYE max 30 m max 300 m A0035252 25 Connection diagram for sensors FDU9x YE yellow BK black RD red BU blue BN brown GNYE green yellow A Grounding at terminal box B Grounding at transmitter FMU95 1 Shielding of sensor cable 2 Terminal box 3 Shielding of extension cable ...

Page 31: ...12 2 YE BK RD 17 16 15 3 YE BK RD 20 19 18 4 YE BK RD 23 22 21 5 YE BK RD 26 25 24 6 YE BK RD 29 28 27 7 YE BK RD 32 31 30 8 YE BK RD 35 34 33 9 YE BK RD 38 37 36 10 YE BK RD FDU Sensor GNYE GNYE Display POWER Sync Fuse 40 39 Service 2 1 3 90 253 VAC 10 5 32 VDC N L PE 1 2 A0038735 26 Potential equalization of metallic sensors in polycarbonate field housing 1 FDU91F 93 95 96 FDU83 84 85 86 2 Termi...

Page 32: ...7 27 Potential equalization of metallic sensors in aluminum field housing 1 FDU91F 93 95 96 FDU83 84 85 86 2 Power supply 3 Potential equalization of supply voltage wired on delivery 4 Protective ground terminal strip with contact to DIN rail 5 Protective ground terminal on outside of field housing Potential equalization of metallic sensors in DIN rail housing Valid for Order code 030 housing mate...

Page 33: ...tion of metallic sensors in DIN rail housing 1 FDU91F 93 95 96 FDU83 84 85 86 2 Metal DIN rail in cabinet 3 Grounding via DIN rail 4 Protective ground terminal strip with contact to DIN rail 5 Terminal strip no contact to DIN rail 6 3 4 Sensor extension cable LWARNING Explosion Hazard Use a terminal box to connect the extension cable If the terminal box is installed in hazardous areas comply with ...

Page 34: ...ble connection cables are available from Endress Hauser 74 6 3 5 Shortening the sensor cable NOTICE Damaged wires or no return conductor may cause malfunctions Do not damage the wires when removing the insulation After shortening the cable twist the shielding metal braiding and connect it to the BK terminal If the cable has a protective ground GNYE do not connect the protective ground to the cable...

Page 35: ...n sensors with a heater 6 3 6 Synchronization terminal Using the GSD files The synchronization terminal must be used if the sensor cables of several transmitters are routed in parallel As a result of synchronization a transmitter cannot receive signals while another transmitter is transmitting signals This prevents transmission and reception signals from mutually influencing one another Number of ...

Page 36: ...idual transmitters Cross section 2 x 0 75 to 2 5 mm2 18 to 14 AWG Cable shield Required for cables 1 m 3 3 ft ground the shield Synchronization wiring diagram Prosonic S FMU90 95 39 40 1 2 3 20 Prosonic S FMU90 95 39 40 Prosonic S FMU90 95 39 40 A0034901 30 Synchronization of multiple FMU90 FMU95 transmitters Prosonic S FMU90 95 39 40 Prosonic FMU860 861 862 63 64 1 2 10 A0034902 31 Synchronizatio...

Page 37: ...splay plug supplied Minimum diameter for cable entry 20 mm 0 79 in 6 3 8 Post connection check Is the terminal assignment correct For field housing polycarbonate aluminum Are the cable glands tight Is the housing cover securely closed For aluminum field housing Is the housing connected to protective ground PE and or the local ground potential PML If the power supply is switched on Is the LED for t...

Page 38: ...ed into one parameter set in the operating menu Each parameter set is identified by a five digit code 3 2 1 33 Identification of the parameter sets 1 Submenu 2 Number of the associated input or output for multi channel devices 3 Number of the parameter set within the submenu 7 1 2 Types of parameter Read only parameters Symbol Cannot be edited Editable parameters Symbol Can be opened for editing b...

Page 39: ...here primary value 6 Name of displayed parameter Symbols for operating state User operating state User parameters can be edited Service parameters cannot be edited Diagnostics operating state Service interface is connected Service operating state User parameters and service parameters can be edited Locked operating state All parameters are locked and cannot be edited Symbols indicating the editing...

Page 40: ...pted The measured value adopts the value specified by the user Output on alarm Off No supply voltage Keys soft key operation The current key function is indicated by soft key symbols above the key Moves the selection bar downwards in a picklist Moves the selection bar upwards in a picklist Opens the selected submenu parameter set or parameter Confirms the edited parameter value Goes to the previou...

Page 41: ...lable if several pages of measured values have been defined see the Display menu Opens the Shortcut menu which contains the most important read only parameters Opens the main menu from where you can access all the device parameters General key combinations 35 Escape 36 Increase contrast 37 Reduce contrast 38 Locking ...

Page 42: ...t parameters Tag marking Envelope curve Language Device information Password reset Middle key current errors If the self monitoring system detects one or more errors the soft key symbol appears above the middle key When the button is pressed a list of all the errors currently pending is displayed Right key Menu main menu Contains all the parameters of the device subdivided into submenus and parame...

Page 43: ... User Organization PNO http www PROFIBUS com CD ROM with all the GSD files for Endress Hauser devices Order No 50097200 Using the GSD files The GSD files must be loaded into a specific subdirectory of the PROFIBUS DP configuration software of the PLC Depending on the software used the GSD files can be either copied to the program specific directory or imported into the database using an import fun...

Page 44: ...ress is displayed in the parameter Output calculation PROFIBUS DP Instrument address Hardware addressing Address Term DP off on off onSW HW 1 2 3 4 5 6 7 8 1 2 3 4 A N 66 B P 65 Address off on SW HW 1 2 3 4 5 6 7 8 A0038436 Hardware addressing takes effect when DIP switch 8 is set to HW off When set to on the position of DIP switches 1 to 7 define the following values in the address Switch 1 value...

Page 45: ... off on off on SW HW 1 2 3 4 5 6 7 8 1 2 3 4 A N 66 B P 65 A B Term off on 1 2 3 4 Term off on 1 2 3 4 A0038437 39 Bus termination on the device A Termination not active B Termination active For the last device on the bus Switch all four terminating switches to on to activate the bus terminating resistor ...

Page 46: ...ty protocol the measuring system FDU9x sensor and FMU9x transmitter is adjusted and the measuring accuracy is optimized for the specified range The Zero distance service parameter is fine adjusted for this adjustment Following a reset this parameter must be re configured in the Service menu according to the data indicated on the 5 point linearity protocol for the FDU9x sensor Please contact Endres...

Page 47: ... para Navigation Level Level LVL N Basic setup LVL N app para Parameter Tank shape Select the applicable option Medium property If the medium cannot be clearly assigned to any of the categories select the Unknown option Process conditions For liquid applications that do not fall into any other category select the Standard liq option For bulk solid applications that do not fall into any other categ...

Page 48: ... E Specify the distance E from the reference point of the sensor to the minimum level zero point The zero point should not be lower than the point where the ultrasonic wave hits the bottom of the tank 9 3 4 Parameter set LVL N full cal Navigation Level Level LVL N Basic setup LVL N full cal Parameter Full F Specify the span F the distance from the minimum level to the maximum level F may not proje...

Page 49: ...rently measured from the zero point to the surface of the product in the selected unit Sensor Displays the distance D currently measured between the sensor membrane reference point of the measurement and the surface of the product A B 1 C D E F A0043335 1 Reference point of measurement A FDU90 without flooding protection tube B FDU90 with flooding protection tube C FDU91 FDU91F D FDU92 E FDU93 F F...

Page 50: ...sat Parameter Type Select the type of linearization see above Customer unit Specify the unit for the linearized value Max scale Specify the maximum vessel content 100 in the selected customer unit Not displayed if Type Table If Type Horizontal cyl or Sphere the Max scale must always refer to a completely full tank Diameter Only displayed if Type Horizontal cyl or Sphere Specify the diameter D of t...

Page 51: ...e is activated Once entered must be activated by the Status table parameter 1 0 0000 0 0000 2 0 0000 0 0000 3 0 0000 0 0000 0 0000 0 0000 A B C A0040751 A Line number B Column for level C Column for values 1 Press to jump to the next line 2 Press to jump to the previous line 3 Press to open the selected line for editing 1 0 0000 0 0000 2 0 0000 0 0000 3 0 0000 0 0000 0 0000 0 0000 A B C A0040752 A...

Page 52: ...hoes that are higher than the mapping curve are evaluated The interference echo is below the mapping curve and is therefore ignored not evaluated Navigation Level Level LVL N Basic setup LVL N check value Parameter Actual distance Displays the distance D currently measured between the sensor membrane and the surface of the product Check distance Compare the distance displayed with the actual value...

Page 53: ...status parameter set appears If the displayed distance is still too small keep recording mapping curves until the displayed distance and the actual distance match Status Specifies the mapping status Enable map The mapping curve is taken into consideration during signal evaluation Disable map The mapping curve is not taken into consideration during signal evaluation but remains stored in the device...

Page 54: ...splay Display 2 Select the type of visualization in the Type parameter see above 3 For Type Value max size or Alter 5x2 val In the Time parameter specify the time after which the next screen is displayed 4 In the Value 1 to Value N parameters select a measured value to be displayed 5 In the Customized text 1 to Customized text N parameters enter a text string to be displayed with the values The sp...

Page 55: ...t calculat Digital input Digital input N Parameter Allocation Select the switching state that is output as a binary signal via the DI Block Relay Connects the DI Block with one of the device relays Once this option has been selected the Relay function is displayed where you can select the relay Pump control Only displayed if pump control has been configured Connects the DI Block with a pump contro...

Page 56: ...or Process Control Devices PROFIBUS specification there are two options for each module AI OUT The module is transmitted in the cyclic data telegram Free Place The module is not part of the cyclic data telegram The option is selected via the configuration tool of the PLC For details see the Operating Instructions of the manufacturer specific configuration tool Modules for digital values DI Each DI...

Page 57: ... B AI 1 Bytes 0 3 Level 1 IEEE754 unit m Byte 4 Status level 1 AI 2 Bytes 5 8 Level 2 IEEE754 unit m Byte 9 Status level 2 AI 3 Bytes 10 13 Level 3 IEEE754 unit m Byte 14 Status level 3 AI 4 Bytes 15 18 Level 4 IEEE754 unit m Byte 19 Status level 4 AI 5 Bytes 20 23 Level 5 IEEE754 unit m Byte 24 Status level 5 AI 6 Bytes 25 28 Level 5 IEEE754 unit m Byte 29 Status level 6 AI 7 Bytes 30 33 Level 7 ...

Page 58: ...ows this value 9 6 Protecting settings from unauthorized access 9 6 1 Software locking Locking 1 Navigate to Device properties Password reset Code 2 Enter a number 2457 The device is locked no entries can be made Unlocking If an attempt is made to change a parameter the device jumps to Password reset Enter 2457 Entries can be made again 9 6 2 Keypad lock Locking Press all three keys simultaneously...

Page 59: ...ing the locking status Navigation Device properties Password reset Status Display options Unlocked All parameters apart from Service parameters can be edited Code locked The device has been locked via the operating menu It can only be unlocked again by entering the access code in the Device settings Password reset Code parameter Key locked The device has been locked via the operating keys It can o...

Page 60: ...d parameter to Turb surface or Add agitator Select another installation position and or a larger sensor During filling emptying the measured value drops sporadically Set the Tank shape parameter to Dome ceiling or Horizontal cyl Avoid a central mounting position for the sensor If possible use a stilling well ultrasound guide pipe Echo loss error E xx 641 Check all the application parameters LVL N ...

Page 61: ... calibration E 5 Right limit of the display range 6 Distance of the evaluated echo measured from the reference point of the sensor 7 Envelope curve solid line 8 Left limit of the display range 9 Marking for full calibration F Scaling the envelope curve display 1 Press the left or middle key The or symbol appears in the top right hand corner of the chart 2 To zoom in press the middle key 3 To zoom ...

Page 62: ...20 1 Click F functions on the menu bar 2 Select the sensor whose envelope curve is to be displayed 3 To display a single curve click the Read curve button 4 To display the curves cyclically press the Cyclic read button 5 In the Curves window select which type of curve is to be displayed envelope curve floating average curve FAC mapping curve ...

Page 63: ... BAD Warning W flashes The device continues to measure The operating status LED flashes red An error message is displayed The status of the output value of the affected AI blocks is UNCERTAIN 10 2 4 Influence of errors on the status byte of the output signal The following table indicates which status the block output values adopt when an error occurs There are three possible status values GOOD UNC...

Page 64: ...re BAD A 0x 641 Distance BAD Temperature GOOD A 0x 651 Distance BAD Temperature GOOD W 0x 651 Distance UNCERTAIN Temperature GOOD A 0x 661 Distance BAD Temperature GOOD W 0x 661 Distance UNCERTAIN Temperature GOOD W 0x 691 Distance UNCERTAIN Temperature GOOD W 0x 802 Distance UNCERTAIN Temperature GOOD Error in the Level Block LE W 0x 601 Level BAD A 0x 604 Level BAD W 0x 611 Level BAD A 0x 671 Le...

Page 65: ...n W 00 103 Initializing please wait If the message does not disappear after a few seconds replace the electronics A 00 106 Downloading please wait Wait for the download to finish A 00 110 Checksum error Total reset and recalibration A 00 111 112 114 115 Electronics defect Switch off device and switch it on again If the error persists call Endress Hauser Service A 00 116 Download error Repeat downl...

Page 66: ...ing Wait for the mapping to finish W xx 521 New sensor xx recognized W xx 601 Linearization curve steps incorrect level xx Enter linearization again Level menu A xx 604 Calibration level xx failure Correct calibration Level menu W xx 611 Less than 2 linearization points for level xx Enter additional linearization points Level menu E xx 641 No usable echo sensor xx Check basic setup for the sensor ...

Page 67: ...troubleshooting Endress Hauser 67 10 3 Firmware history V01 00 00 04 2007 Original software BA00344F 00 en 05 06 V01 01 00 06 2006 Integration of the FDU90 sensor BA00344F 00 en 07 09 V01 01 03 05 2011 New option binary inputs BA00344F 00 en 13 12 ...

Page 68: ...U95 PROFIBUS DP 68 Endress Hauser 11 Maintenance No special maintenance work is required 11 1 Exterior cleaning When cleaning the exterior always use cleaning agents that do not corrode the surface of the housing and the seals ...

Page 69: ...ed device version by Endress Hauser Service only Document all repairs and modifications 12 1 3 Replacing a device or electronics module After an entire device or an electronics module has been replaced the parameters can be downloaded to the device again via the communication interface For this the data must have been uploaded to the PC beforehand using the FieldCare software You can continue meas...

Page 70: ...e device if repairs or a factory calibration are required or if the wrong device was ordered or delivered 12 4 Disposal Observe the following notes during disposal Observe valid federal national regulations Ensure proper separation and reuse of the device components ...

Page 71: ...e USB port of a computer Order number 51516983 Additional information Technical Information TI00405C 13 2 Device specific accessories 13 2 1 Weather protection cover for polycarbonate field housing 278 10 9 227 8 94 194 7 64 A0034922 51 Weather protection cover for polycarbonate field housing Unit of measurement mm in Material 316Ti 1 4571 Mounting and fixing using the Prosonic S housing bracket O...

Page 72: ...er 25 to 50 mm 1 to 2 in Dimensions 210 x 110 mm 8 27 x 4 33 in Material 316Ti 1 4571 Mounting accessories fastening clips screws and nuts are supplied Order number 52024478 Frame 700 mm 27 6 in 3 2 0 13 20 0 8 55 2 17 100 3 94 25 0 98 700 27 6 45 1 77 76 2 99 100 3 94 200 7 87 13 0 5 ø33 7 1 3 130 5 12 150 5 91 100 3 94 60 2 36 4 0 16 6 5 0 3 109 4 29 75 2 95 A0037799 53 Dimensions Unit of measur...

Page 73: ...rame 1400 mm 55 1 in 3 2 0 13 20 0 8 55 2 17 100 3 94 25 0 98 1400 55 1 45 1 77 76 2 99 100 3 94 200 7 87 13 0 5 ø33 7 1 3 130 5 12 150 5 91 3 94 60 2 36 4 0 16 6 5 0 3 109 4 29 75 2 95 100 A0037800 54 Dimensions Unit of measurement mm in Weight 6 0 kg 13 23 lb Material 316L 1 4404 Order number 71452326 ...

Page 74: ...ts surges induced or generated in the system Additional information Technical Information TI01012K 13 2 5 Extension cables for sensors Maximum permissible total length sensor cable extension cable 300 m 984 ft The sensor cable and extension cable are the same type of cable FDU90 FDU91 without sensor heater Cable type LiYCY 2x 0 75 Material PVC Ambient temperature Order number 71027742 FDU90 FDU91 ...

Page 75: ...Prosonic S FMU95 PROFIBUS DP Accessories Endress Hauser 75 FDU95 Cable type Li2G2G 2x 0 75 D 1x0 75 Material silicone Ambient temperature 40 to 150 C 40 to 302 F Order number 71027745 ...

Page 76: ...l cal Full F Blocking distance Parameter set L1007 LVL N unit Unit level Level N Distance Parameter set L1008 LVL N linearisat Type Customer unit Customized text Max scale Diameter Intermediate height H Mode Edit Status table Parameter set L100B LVL N check value Act distance N Check distance Parameter set L100B LVL N dist map Act distance N Range of mapping Start mapping Status Parameter set L100...

Page 77: ...ettings Parameter set AX102 Outp echo loss Level N Ramp level N Value level N Parameter set AX103 Delay echo loss Delay Sensor N Parameter set AX104 Safety distance Saf dist sen N Parameter set AX105 In safety dist In saf dist s N Reset sen N Parameter set AX107 React high temp Overtemp sen N Max temp sen N Parameter set A0000 Defect temp sen Def temp sen N 14 3 Overview of the Output calculat men...

Page 78: ...u Password reset Parameter set D1104 Password reset Reset Code Status 14 5 Menu System informat 14 5 1 Submenu Device information Parameter set IX101 Device family Device family Parameter set IX102 Device name Device name Parameter set IX103 Device marking Device marking Parameter set IX105 Serial no Serial number Parameter set IX106 Software version Software version Parameter set IX107 Dev rev De...

Page 79: ...c presentation 14 5 5 Submenu Error list Parameter set E1002 Actual error 1 2 Parameter set E1003 Last error 1 2 14 5 6 Submenu Diagnostics Parameter set E1403 Operating hours Operating hours Parameter set E1404 Actual distance Act distance N Parameter set E1405 Act meas value Level N Parameter set E1405 Application par Sensor N Parameter set E1406 Echo quality sen Echo quality N 14 6 Menu Display...

Page 80: ...nu Prosonic S FMU95 PROFIBUS DP 80 Endress Hauser 14 7 Menu Sensor management 14 7 1 Submenu Sensor management FDU sensor N Parameter set D1106 US sensor N Sensor operation Sensor priority Detected Detection window ...

Page 81: ......

Page 82: ......

Page 83: ......

Page 84: ...www addresses endress com 71526736 71526736 ...