Coding
Field
Selection or range
Factory setting
Display
Info
R2 (3)
P(ID) controller
configuration
LC PV =
limit contactor cd (1)
LC °C =
limit contactor T (2)
PID controller
(3)
Timer (4)
Clean =
Chemoclean (5)
USP23 (6)
R231
Switch function of
R3 (3) off or on
Off
On
R232
Enter set point
cond/ind:
0.00 µS/cm
MOhm:
0.00 k
Ω⋅
cm
conc:
0.00 %
entire meas. range
The set point is the value to be
maintained by the control. This
value is to be re-established by
the control in the event of any
deviation (up or down).
R233
Enter control gain
K
p
1.00
0.01 ... 20.00
See chpt. 5.5.2.
R234
Enter integral
action time T
n
(0.0 = no I comp.)
0.0 min
0.0 ... 999.9 min
See chpt. 5.5.2.
At every hold, the I comp. is
set to zero.
Hold can be deactivated in
S2, but not for Chemoclean
and Timer.
R235
Enter derivative
action time T
v
(0.0 = no D comp.)
0.0 min
0.0 ... 999.9 min
See chpt. 5.5.2.
R236
Selection of
controller
characteristic
dir
=
direct
inv = inverted
Setting may or may not be
required depending on control
deviation (up or down deviation,
see chpt. 5.5.2).
R237
Selection of pulse
length or pulse
frequency
len
=
pulse length
freq = pulse frequency
Pulse length e.g. for solenoid valve,
pulse frequency e.g. for solenoid-
operated metering pump (see
chpt. 5.5.2).
R238
Enter pulse interval
10.0 s
0.5 ... 999.9 s
This field only appears if pulse
length is selected in R237. When
pulse frequency is selected,
R238 is skipped and input
continues in R239.
Factory settings are printed in
bold
face;
base version does not include functions in italics.
PID
R2
Sel. Type
Off
R231
Function
0.00
µS/cm
R232
Setpoint
1.00
R233
Kp
0.0
R234
Time Tn
min
0.0
R235
Time Tv
min
dir
R236
Direction
len
R237
Oper.Mode
10.0
R238
PulsePer.
s
Instrument configuration
Liquisys M CLM 223 / 253
38
Hauser