EAOM-210 FLJ.eng / ver 0.0
Pages 85 / 132
RETURN DELAY
This timer dictates how long the module will wait before it will un-load the generator (back to
the mains supply if AMF) and initialise it’s run-on and shutdown cycle. This is ensure that the
mains supply has stabilised before transferring the load back to mains.
COOLING TIMER
This is the time the generator is to run off-load once the load transfer signal has ceased. This
gives the engine time to cool down before shutdown.
GENERATOR FREQUENCY ERROR CONTROL TIME
If firstly generator frequency is out of under and over set points this timer is initiated. If
generator frequency is out of under and over set points when this timer expires a ‘generator
frequency error’ alarm signal is generated.
GENERATOR VOLTAGE ERROR CONTROL TIME
If firstly generator voltage is out of under and over set points this timer is initiated. If
generator voltage is out of under and over set points when this timer expires a ‘generator
voltage error’ alarm signal is generated.
FAIL TO STOP TIME
Once the module has given a shutdown signal to the engine it expects the engine to come to
rest. It monitors the Oil pressure and speed sensing sources and if they still indicate engine
movement when this timer expires a ‘Fail To Stop’ alarm signal is generated.
(BREAKERS PAGE) BREAKERS page
HARDW.BREAKER SELCT
Hardware Breaker Selection
0 – 2
0
GEN.CLOS.BREK.C.TYP
Gen Close Breaker Contact Type
NO/NC
0 – 1
0
GEN.CLOS.BREK.R.TYP
Gen Close Breaker Relay Type
NOR/PULS
0 – 1
0
GEN.CLOSE TIMER
Gen Close Timer
Sec
1 – 250
5
GEN.OPEN.BREK.C.TYP
Gen Open Breaker Contact Type
NO/NC
0 – 1
0
GEN.OPEN.BREK.R.TYP
Gen Open Breaker Relay Type
NOR/PULS
0 – 1
0
GEN.OPEN TIMER
Gen Open Timer
Sec
1 – 250
5
MAIN CLS.BREK.C.TYP
Main Close Breaker Contact Type
NO/NC
0 – 1
0
MAIN CLS.BREK.R.TYP
Main Close Breaker Relay Type
NOR/PULS
0 – 1
0
MAINS CLOSE TIMER
Mains Close Timer
Sec
1 – 250
5
MAIN OPN.BREK.C.TYP
Main Open Breaker Contact Type
NO/NC
0 – 1
0
MAIN OPN.BREK.R.TYP
Main Open Breaker Relay Type
NOR/PULS
0 – 1
0
MAINS OPEN TIMER
Mains Open Timer
Sec
1 – 250
5
BREKR.CLOS.PULS.TIM
Breaker Close Pulse Time
Sec
0.0 – 10.0
0.5
BREKR.OPEN.PULS.TIM
Breaker Open Pulse Time
Sec
0.0 – 10.0
0.5
TRANSFER TIME
Transfer Time
Sec
0 - 250
2
HARDWARE BREAKER SELECTION
0-
Mains and Gen schalters have only close drives and if close drive off schalter will open.
Parameters;
GEN CLOSE BREAKER CONTACT TYPE, GEN CLOSE TIMER(if gen closed
input selected), GEN OPEN TIMER(if gen closed input selected), MAIN CLOSE BREAKER
CONTACT TYPE, MAINS CLOSE TIMER(if mains closed input selected), MAINS OPEN
TIMER(if mains closed input selected), TRANSFER TIME.