EAOM-210 FLJ.eng / ver 0.0
Pages 125 / 132
5.6 Test Operation
Press the
Test
(28)
button to select Test mode the LED (11) will light on. This mode allows
for testing of the generator off load. All alarm circuits will operate so that any faults will
be reported. If a mains failure occurs while the unit is in Test mode, the unit will revert to
Auto mode and will switch the load to the generator.
5.6.1 Exercise Function
Please enter the day of the week for Exercise Function. Example:
EXER.WORKING PERIOD
(dis)0
The exercise function is disabled.
(10)
The exercise function is enabled for 10 minutes.
EXER.WR.DAY OF WEEK
1=Monday.
EXER.WORK.START TIM
12.20
The exercise function is every Monday started at
12.20 o’clock. (if it is enabled)
When the Real-Time clock reached to the Generator Exercise Work Start Time (12.20
o’clock) if the unit is in “AUTO MODE” and Mains is available the unit changes running
mode to the “TEST MODE” automatically and starts the engine. The time period of engine
running is counted and compared with value of Generator Exercise Working Period
parameter (10 minutes). (If the engine does not run time is not counted). If the period is
completed the unit changes run mode to “AUTO” automatically. When the unit is in the
“TEST MODE” if the Mains is gone, the unit will change run mode to “AUTO MODE”
automatically.