EAOM-210 FLJ.eng / ver 0.0
Pages 61 / 132
(EXP.CNF.INPUT-8 PAGE) EXPANSION CONFIGURABLE INPUT (8) page
DIS,USERCNF.OR LIST
0- Disable
1- User Configured
2- Select From List
(dis)0 - 2
1
HARDWARE TYPE
Hardware type:
(0 = -Ve, 1 = +Ve)
0 - 1
0
POLARITY
0- Normally Open (Close To Activate)
1- Normally Close (Open To Activate)
0 - 1
0
INDICATION
If User Configured
0- Status
1- Warning Non-Latching
2- Warning Latching
3- Electrical Trip
4- Shutdown
0 – 4
0
ACTIVATION
If User Configured
0- Active From Starting
1- Active From Safety On
2- Always Active
0 – 2
2
SELECT FROM LIST
If Select From List
1 Auxiliary Mains Fail
2 Simulate Lamp Test Button
3 Simulate Horn Reset Button
4 Simulate Alarm Reset Button
5 Simulate Off Button
6 Simulate Auto Button
7 Simulate Test Button
8 Simulate Manual Button
9 Simulate Start Button
10 Simulate Stop Button
11 Generator Closed Auxiliary
12 Generator Load Inhibit
13 Mains Closed Auxiliary
14 Mains Load Inhibit
15 Auto Restore Inhibit
16 Auto Start Inhibit
17 Panel Lock
18 Scheduled Runs Inhibited
19 Reset Maintenance Alarm
20 Transfer To Generator/Open Mains
21 Transfer To Mains/Open Generator
1 – 21
2
INPUT TIME DELAY
Input active delay
SEC
0 - 250
5
CONFIGURABLE INPUTS SELECTIONS
0 REMOTE START/STOP
In AUTO mode, if one of the configurable inputs are selected as 0 (Remote Start), the
module doesn’t perform the mains failure control in order to start the generator. In AUTO
mode, if one of the configurable inputs are selected as 0 (Remote Start) and this input is
active, then the module will perform the start sequence. If the input is passive module will
perform the stop sequence.
1 AUXILIARY MAINS FAIL
The EAOM-210 FLJ module will monitor the incoming single or three phase supply for Over
Voltage, Under Voltage, Over Frequency or Under Frequency. It may be required to monitor
a different mains supply or some aspect of the incoming mains not monitored by the EAOM-
210 FLJ. If the devices providing this additional monitoring are connected to operate this
input, the EAOM-210 FLJ will operate as if the incoming mains supply has fallen outside of
limits, the generator will be instructed to start and take load. Removal of the input signal will
cause the module to act if the mains has returned to within limits.